Clay, Lynn: Below are our responses in red to the building inspections comments, and attached are the associated sheets: 1. Special inspector required for structural elements and wind turbine installation. – Noted 2. All construction shall comply with 2006 IEEC. Submit Com-ck sheets for elec, plmb, mech and building envelope showing compliance. – Final signed Com-ck sheets was submitted via e-mail to you this morning. 3. All glazing shall comply with CH 24 2006 IBC. – The specified glazing is in compliance with 2006 IBC. Please see attached Spec Section 08800. 4. Elec riser diagram on Sheet EP-3 doesn’t show size of pipe or grounding electrode system. – Items now shown, see attached Sheet EP-3 5. Sheet EP-3 shows panel LA with 225 amp protection and Sheet E-5 shows 600 amps. – Sheets EP-3 and E-5 now coordinated, see attached sheets. 6. Where will power company pad mount transformer be located? – Location now shown on site plan, see attached Sheet E-2, note 11. 7. Lighting control panel not shown on all floor plans. – Lighting panel now shown on floor plans, see attached Sheets E-3 and EP-2. 8. Panic hardware required on both exits. – Panic hardware specified for both exit doors. See attached Spec Section 08710. 9. I would like to speak with the Double E. – John Manning at (817) 735-7342 Thanks, Ron Please consider the environment before printing this message. ________________________________ This electronic mail message is intended exclusively for the individual or entity to which it is addressed. This message, together with any attachment, may contain the sender's organization's confidential and privileged information. The recipient is hereby notified to treat the information as confidential and privileged and to not disclose or use the information except as authorized by sender's organization. Any unauthorized review, printing, retention, copying, disclosure, distribution, retransmission, dissemination or other use of, or taking of any action in reliance upon, this information by persons or entities other than the intended recipient is prohibited. If you received this message in error, please immediately contact the sender by reply email and delete all copies of the material from any computer. Thank you for your cooperation.