New RFI No. 15 As of 23-Jun-2010 2:34 PM CT Vitruvian Infrastructure Phase 1C Park 4010 Marsh Lane Addison, Texas 75001 Project Number: 1308C Status: Outstanding Subject Electrical Reason Code None Question 1. Sheet C802 shows two irrigation controllers on panel VPEP2-20. The panel schedule for VPEP designates circuit 7 for irrigation controllers. The plans do not show conduit and wire for these. 2. On Sheet C803, the recirculating and irrigation pump control pedestal shows a pad and electric service meter. Do we mount a meter on the side of the control panel? Does it need a main to fuse control panel? 3. From the bid set to the construction set, approx. 580 lf of conduit changed from 3/4" to 1-1/4" that serves pole lights from Ponte Avenue to the south pedestrian bridge. 4. Do we install a small pier or do we embed Pedloks in concrete? Proposed Solution Attached Files (none) Section: 16 - Electrical Int. Tracking #: Days Elapsed: 0 From: Jennifer Haynes Originated: 23-Jun-2010 2:34 PM CT To: Nick Jacob (First Recipient) Requested By: 26-Jun-2010 2:19 PM CT Copy to: Eric Little Wade Geistweidt Bruce Dunne Clay Barnett Additional Info Proposed Solution Impact Critical Path? No Cost Change: Yes, may be Time Change: None Discipline Code: Electrical Drawing Numbers: C802,C803 Needs Drawing Change? Yes History (Chronological Order) No history to display. Final Response (Closing) This item is still open. No final response to display. .................................................................................. Copyright (c) 1999-2010, Systemates, Inc. View the User Agreement for legal restrictions and terms of use applicable to this site. Use of this site signifies your agreement to the terms of use specified in the User Agreement. Projectmates - The Capital Project Management Software