>> Leave comment << Response to Construction Submittals No. 10 As of 18-Apr-2011 10:39 AM CT Vitruvian Infrastructure Phase 2A - Bella Lane 3900 Vitruvian Way Addison, Texas 75001 Project Number: 1308 - 2A Status: Outstanding Product Classification Category 16000 - ELECTRICAL (03 - Product Data) Attachment(s) Electrical Conduit cover sheet- signed.pdf Electric Conduit & Spacers submittal.pdf Notes Description Electric Conduit and Spacers Certification Section: 16 - Electrical Int. Tracking #: Submitted by: Lauren Williams Issue Date: 18-Apr-2011 10:09 AM CT Est. Delivery Date: 18-Apr-2011 Actual Date Received: Sent To: Eric Little (First Recipient) Requested By: 9-May-2011 9:45 AM CT Copy to: Paul Roy Joel Massey Robert Farrow History (Chronological Order) Type Routed Memo Lauren, Per Oncor, this submittal is rejected: Joel, "Oncor Standards accepts the Heritage Plastics conduit for duct bank use as long as it has at least the wall thickness of the DB-60 (.182” for 6”). The EB-20 is not acceptable. Oncor Standards does not accept the Heritage Plastics spacers. These are not interchangeable with the spacers supplied by our other accepted manufacturers. Please contact me if you have any questions. Thank you, James Davis Oncor Electric Delivery 214.486.3280" Please revise and resubmit. Attached Files (none) Submittal Type: 12 - Other Sent By: Eric Little Date Sent: 18-Apr-2011 10:39 AM CT To: Lauren Williams Requested By: 9-May-2011 9:45 AM CT Copy to: Paul Roy Joel Massey Nick Jacob Scott Hale Robert Farrow Clay Barnett Final Action No final action to display. Comments .................................................................................. Copyright (c) 1999-2011, Systemates, Inc. View the User Agreement for legal restrictions and terms of use applicable to this site. Use of this site signifies your agreement to the terms of use specified in the User Agreement. Projectmates - The Capital Project Management Software