_8FIRE DEPARTMENT (214)450-7200 FAX (214)450-7208 ADDIsoN ip.. i %SPAi!¥Wl¥ hlP • d 0 i, " PG8t Office Box 144 Addison, Texas 15001 4198 Airport Parkway MAXI-LIFT INC. SPECIFICATION SUMMARY INDEX Document A Maxi-Lift Inc. letter and proposal to Fire Dept. requesting waiver in code requirements. Fire Dept. ! memos and response letter. I DocumentB Portions ofArticle 81 of 1991ed. Uniform Fire Code which is adopted by city and enforced by Fire Department. These sections show the requirement for smoke and heat venting as for this application. DocumentC Formal interpretation of the Uniform Fire Code from International Fire Code Institute. Pursuant to the removal of smoke and heat vents. International Fire Code Institute, this organization is responsible for writing the fire codes. DocnmentD Portions ofthe 1994ed. Uniform Fire Code, Article 81. This edition has not been adopted by city as of now. However, this edition should be adopted early in 1995. This edition contains the same requirements for smoke and heat venting in regards to this application. Please note D-14 to D-16. This is the Uniform Fire Code Standards concerning smoke and heat venting. The Standards Manual gives explanations and interpretations to the code. DocumentE National Fire Protection Association (NFP A) standards for ESFR sprinkler systems. This standard illustrates the many different standards that address an ESFR system. DocumentF NFPA standard for warehousing. F-2 addresses smoke and heat venting. DocumentG Factory Mutual study presented by Maxi-Lift as the basis oftheir request. 1 I Maxi-lift.inc. AUGUST 17, 1994 MAXI-LIFT, INC. PROPOSED WAREHOUSE AND MIDWAY ROAD, ADDISON, MANUFACTURING TEXAS FACILITY SUBJECT: FIRE CODES ON SMOKE VENTS AND DRAFT 􀁓􀁕􀁒􀁒􀁏􀁾􀁾􀁉􀁎􀁇􀀠THE CITY OF ADDISON. CURTAINS OF CITIES 1) DAVID SESSIONS CITY OF DALLAS (CODE SUPERVISOR) -948-4480 THE CITY OF DALLAS REMOVED CURTAINS IN BUILDINGS THAT ALL CODE REQUIREMENTS FOR SMOKE VENTS AND HAVE ANY TYPE SPRINKLER SYSTEM IN 1985. DRAFT 2) CHARLES HOSEY (FIRE CHIEF) CITY OF CARROLLTON -466-3070 ELIMINATED THE CODE REQUIREMENTS FOR SMOKE VENTS AND DHAFT CURTAINS WHEN USING AN ESFR SPRINKLER SYSTEM. STILL REQUIRE MELT DROP OUT PANELS (WHICH ARE MUCH CHEAPER THAN SMOKE VENTS). 3) STEVE BOONE (CODE SUPERVISOR) CITY OF RICHARDSON -238-4160 SMOKE VENTS ONLY REQUIRED WITH A SPACE GREATER THAN 250 FEET FROM AN EXIT DOOR. MAXI-LIFT'S WAREHOUSE HAS NO AREA GREATER THAN 250 FEET FROM DOOR AND THUS WOULD NOT BE REQUIRED TO USE SMOKE VENTS. NO DRAFT CURTAINS ARE REQUIRED BY CITY CODE. 4) HAY KIRBY (BUILDING CODE CITY OF PLANO -578-7209 OFFICAL) PLANO IS IN THE PROCESS OF REVISING CODE REQUIREMENTS IN VIEW OF THE SYSTEM AND IS CURRENTLY GIVING RELIEF TO PROPOSED BUILDING OWNERS ON CASE BASIS. ESFR SPRINKLER A CASE BY FURTHER: PER THE ATTACHED INFORMATION, FACTORY MUTUAL STATES THAT AS A RESULT OF THEIR TESTING, SMOKE VENTS SHOULD BE AVOIDED WHEN USING AN ESFR SPRINKLER SYSTEM. THEY MAY, IN FACT, EVEN FUEL THE FIRE UNDER CERTAIN CONDITIONS. CONCLUSION: I BELIEVE THE ABOVE INFORMATION CLEARLY INDICATES THE RE-EVALUATE THEIR SMOKE VENT FIRE CODE POLICY, AS ALL US HAVE. CITY OF ADDISON NEEDS TO THE CITIES SURROUNDING P.O. BOX 11-0518 • CARROllTON, TEXAS 75011·0518 1223 CROWLEY DRIVE. CARROllTON. TEXAS 75006 (214) 245·2542 U.S. WATS (800) 527·0657 08/02/94 14:16 'a'214 661 1402 FACTORY 􀁾􀁉􀁕􀁔􀁕􀁁􀁌􀀠 , 􀀱􀀴􀁬􀁾􀀠 o 0 "(tv o Factory Mutual Engineering FAX TRANSMISSION MEMORANDUM DATE: August 1, 1994 PLEASE DELIVER THE FOLLOWING MESSAGE TO: NAME: Mr. Vic Sahm COMPANY: Maxilift FAX: 242-8203 RE: Smoke Vents with ESFR Sprinkler Protection De«;r Mr. Sahm: 12222 Merit Drive, Swite 1800 De'la•. Texas 75251·3209 Telephone !2141 661·9202 rax (214) 661-1402 I have enclosed page 2 from the Factory Mutu«l Data Sheet 2-2. Please refer to the marked p«ragraphs. The data sheet indicates from testing it has been concluded that smokes vents «re not needed for ESFR sprinkler protection. Also the ESFR sprinkler design will not «llow a fire to produce «s much smoke as conventional sprinklers since ESFR protection is considered a suppression mode type protection where as conventional sprinklers are of the control mode. This means ESFR's are designed to put out a fire where-as conventional sprinklers are only designed to control the fire until manual fire fighting can extinguish it. Per our conversation you indicated some interest in finding 􀁭􀁯􀁲􀁥􀁾􀀠about one of our insurance companies. I have listed the name of the insurance company and « contact. If you should have any further questions please feel free to call. Regards, 􀀻􀀿􀀿􀀴􀀯􀁾􀁾􀁾􀀮􀀠 Michael P. Herrmann Loss Prevention Consultant Dallas District Office Encl: page 2 of D.S. 2-2 MPH/mph 􀁁􀀭􀀩􀀯􀁾􀁊􀀮􀀮􀀠... Ie... 􀁾􀁉􀀠J::rt 􀁓􀁾􀁲􀀺􀀺􀀠 qq /-3737 􀀢􀀯􀁾􀀬􀂣􀁴􀀠 , o ., o " 08/02194 14:17 '5"214 661 1402 FACTORY MUTUAL 􀁦􀁩􀀡􀁊􀁏􀁏􀁾􀀠 required by the code, and should a flre occur in the bUilding which is not controlled by the sprinklers, it may require an 'inordinate demdon'!Itre suppression forcesJto contain the fire to the warehouse. A reduction in draft curtains commensurate with the revisions for ESFR Systems in the 1994 Code would be reasonable. 1994 UNIFORM FIRE CODE 8101-8101.3.2 ARTICLE 81 -HIGH-PILED COMBUSTIBLE STORAGE SECTION 8101 -GENERAL 8101.1 Scope. Buildings containing high-piled combustible storage shall be in accordance with Article 81. In addition to the requirements of Article 81, aerosols shall be in accordance with Article 88, flammable and combustible liquids shall be in accordance with Article 79, and hazardous materials shall be in accordance with Article 80. 8101.2 Definitions. 8101.2.1 General. For definitions of AEROSOL; ARRAY; ARRAY, CLOSED; BINBOX; COMMODITY; CURTAIN BOARD; EARLY SUPPRESSION FAST-RESPONSE SPRINKLER; EXPANDED PLASTIC; EXTRAHIGH-RACK COMBUSTIBLE STORAGE; HIGH-PILED COMBUSTIBLE STORAGE; LONGITUDINAL FLUE SPACE; MANUAL STOCKING METHODS; MECHANICAL STOCKING METHODS; SHELF STORAGE; AND TRANSVERSE FLUE SPACE, see Article 2. 8101.2.2 Limited application. For the purpose ofArticle 81, certain tenns are defined as follows: HIGH-PILED STORAGE AREA is an area within a building which is designated, intended, proposed or or actually used for high-piled combustible storage. SOLID SHELVING is shelving that is solid, slatted, mesh, or grated located within racks that obstructs sprinkler water penetration through the racks. 8101.3 Permits and Plan Submittal. I, 810l.3.1 Permits. For a pennit to use a building for 􀁨􀁩􀁧􀁨􀁾􀁰􀁩􀁬􀁥􀁤􀀠combustible storage, see Section 105, Permit h.3. 8101.3.2' Plans and specifications submittal. At the time of pennit application, plans and 􀁳􀁰􀁥􀁣􀁩􀁾􀀠 fications including the infonnation specified in Section 8101.3.2 shall be submiued for review and approval. Following approval of the plans, a copy of the approved plans shall be maintained on the premises in an approved location. The plans shall include the following: 1. Floor plan of the building showing locations and dimensions of high-piled storage areas. 2. Useable storage height for each storage area. 3. Number of tiers within each rack, if applicable. 4. Commodity clearance between top of storage and the sprinkler deflector for each storage arrangement. 5. Aisle dimensions between each storage array. 6. Maximum pile volume for each storage array. 7. Location and classification of commodities in accordance with Section 810 t A. 8. Location of commodities which are banded or encapsulated. 9. Location of required fire department access doors. 10. Type of 􀁦􀁩􀁲􀁥􀁾􀁳􀁵􀁰􀁰􀁲􀁥􀁳􀁳􀁩􀁯􀁮􀀠and 􀁦􀁩􀁲􀁥􀁾􀁤􀁥􀁴􀁥􀁣􀁴􀁩􀁯􀁮􀀠systems. 11. Location of valves controlling the water supply of ceiling and 􀁩􀁮􀁾􀁲􀁡􀁣􀁫􀀠sprinklers. 12. Type, location and specifications of 􀁳􀁭􀁯􀁫􀁥􀁾􀁲􀁥􀁭􀁯􀁶􀁡 􀁬􀀠and curtain board systems. 13. Dimension and location of transverse and longitudinal flue spaces. 14. Additional infonnation regarding required design features, commodities, storage arrangement and fire-protection features within the 􀁨􀁩􀁧􀁨􀁾􀁰􀁩􀁬􀁥􀁤􀀠slOrage area shall be provided at the time of pennit, when required by the chief. 1-349 8101.3.3-8101.4.1.3 1994 UNIFORM FIRE CODE 8101.3.3 Evacuation 􀁰􀀩􀁡􀁮􀁾􀀠When required by the chief, an evacuation plan for public accessible areas and a separate set of plans indicating location and width of aisles, location of exits and exit signs. height of storage, and locations of hazardous materials shall be submitted 8l the time of permit application for review and approval. Following approval of the plans, a copy of the approved plans shall be maintained on [he premises in an approved location. 8101.4 Commodity Classification. 8101.4.1 General. 8101.4.1.1 Classification of commodities. Commodities shall be classified as Class I, II, m.IV or high hazard in accordance with Section 8101 A.l. Materials listed within eachcommodilY classification are assumed to be unmodified for improved combustibility characteristics. Use of flameretarding modifiers or the physical form of the material could change the classification. See Section 8101.4.2 for classification of Groups A. Band C plaslics. 8101.4.1.2 Class f commodities. Class I commodities are essentially noncombuSlible products on wooden or nonexpanded polyethylene solid deck pallets. in ordinary corrugated cartons with or without single-thickness dividers, or in ordinary paper wrappings with or without pallets, Class I commodities are aUowed to contain a limited amount ofGroup A plastics in accordance with Section 8101.4.3. Examples of Class I commodities include, but are not limited to, the following: Alcohotic beverages nOt exceeding 20 percent alcohol Appliances-noncombustible. electrical Cement in bags Ceramics Dalry products in 􀁮􀁯􀁮􀁷􀁡􀁸􀁾􀁣􀁯􀁡􀁴􀁥􀁤􀀠containers {excluding bOllles) Dry insecticides Foods in noncombustible containers Fresh fruits and vegetables in nooplastic trays or containers Frozen foods Glass Glycol in metal cans Gypsum board Inert materials. bagged Insulation, noncombustible Noncombustible liquids in plastic containers having less than a 5-gnllon (18.9 L) capacity Noncombustible metal products 8101.4.1.3 Class n commodities. Class II commodities are Class I products in slaned wooden crates, soUd wooden boxes, multiple-thickness paperboard cartons or equivalent combustible packaging material with or without pallets. Class II commodittes are allowed to contain a limited amount of Group A plastics in accordance with Section 810 I ,4.3. Examples of Class II commodities include. but are not limited to. the rollowing: Alcoholic beverages not exceeding 20 percent alcohol, in combustible containers Foods in combustible containers Incandescent or fluorescent light bulbs in cartons Thinly coated fine wire on reels or in cartons 1-350 1994 UNIFORM FIRE CODE 8101.4.1._101.4.1.5 8101.4.1.4 Class III commodities. Class III commodities are commodities of wood. paper,natural fiber cloth, orGroup C plasticsorproduc[s thereof, with or wilhout pallets. Products are allowed to contain Umited amounts of Group A or B plastics, such as metal bicycles with plastic handles, pedals, seats and tires. Group A plastics shall be limited in accordance with Section 8101.4.3. Examples of Class III commodities include. but arc not limited to, the following; Aerosol, Levell (see Article 88) Combustible fiberboard Cork, baled Feed. bagged Fertilizers, bagged Food in plastic containers Furniture: wood, natural fiber. upholstered, nonpiastic, wood or metal with 􀁰􀁬􀁡􀁳􀁴􀁩􀁣􀁾􀁰􀁡􀁤􀁤􀁥􀁤􀀠and covered ann rests Glycol in combustible containers not exceeding 25 percent Lubricating or hydraulic fluid in metal cans Lumber Mattresses, excluding foamed rubber and foamed plastics Noncombustible liquids in plastic comainers having a capacity of more than 5 gallons ( 18.9 L) Paints, oil base, in metal cans Paper. waste, baled Paper and pulp, horizontal storage, or vertical storage that is banded or protected with approved wrap Paper in cardboard boxes Pillows. excluding foamed rubber and foamed plastics Plastic-coaled paper food containers Plywood Rags, baled Rugs, without foamed backing Sugar, bagged Wood, baled Wood doors, frames and cabinets Yams of natural tiber and viscose 8101.4.1.5 ClaSs IV commodities. Class IV commoditieS:.re Class 1.11 or HI products containing' Group A 'plastics in ordinary corrugated carrons-and Classes I. nand HI products, with Group A plastic packaging, with or without pallets. Group B plastics an"d free-flowing Group A plastics are also induded in this class ..The total amount of nonfree-f1owing Group A plastics shall be in 􀁡􀁣􀁣􀁯􀁲􀁾􀀠 dance wirh Section 8101.4.3, Examples of Class IV commodities include, but are not limtted to. the following: Aerosol. Level 2 (see Article 88) Alcoholic beverages, exceeding 20 percent but less than 80 percem alcohol. in eans or botlles in canons Clothing. symhetic or nonviscose 1-351 8101.4.1.5-810'.4.2.2 1994 UNIFORM FIRE CODE Combustible metal products (solid) Furniture, plastic upholstered Furniture. wood or metal with plastic covering and padding Glycol in combustible containers (greater than 25 percent and less than 50 percent) Linoleum products Paints, oil base in combustible containers Pharmaceutical, alcoholic elixirs. tonics, etc. Rugs, foamed back Shingles, asphalt Thread or yam. synthetic Or nonviscose 8101.4.1.6 High-hazard commodities. High-hazard commodities are high-hazard products presenting special fire hazards beyond those of Class I, JI, 1Il or IV. Group A plastics not otherwise classified are included in this class. ExampJes of high-hazard commodities include. but are not limited to, thc following: Aerosol, Level 3 (see Article 88) Alcoholic beverages, exceeding 80 percent alcohol, in bottles or cartons Flammable solids (except solid combustible metals) Glycol in combustible containers (50 percent or greater) Lacquers, which dry by solvent evaporation, in metal cans or cartons Lubricating or hydraulic Ouid in plas:tic containers Mattresses. foamed rubber or foamed plastics Pallets and flats which are idle combustible Paper, asphalt, rolied, horizontal storage Paper, asphalt, rolled, vertical storage Paper and pulp, rolled, in vertical storage which is unbanded or not protected with an approved wrap Pillows, foamed rubber and foamed plastiCS Pyroxylin Rubber tires Vegetable oil and butter in plastlc containers 8101.4.2 Classification of plastics. 8101.4.2.1 General. Plastics shall be designated as Group A, B or C in accordance with Section 8101.4.2. 8101.4.2.2. Group A plastics: Group A plastics are plastic materials having a heat of combustion that IS much higher than that ofordinary combustibles, and a burning rate higher than that ofGroup B plastiCS. Examples of Group A plastics include. but are not limited to, the following: ABS (acrylonitrile-butadiene-styrene copolymer) Acetal (polyformaldehyde) Acrylic (polymethyl methacrylate) Butyl rubber 1-352 1994 UNIFORM FIRE CODE 8101.4.2.2-8101.4.3 EPDM (ethylene-propylene rubber) FRP (fiberglass·reinforced polyester) Natural rubber (expanded) Nitrile rubber (acrylonitrile-butadiene rubber) PET or PETE (polyelhylene terephthalate) Polybutadiene Polycarbonate Polyester elastomer Polyethylene Polypropylene Polyslyrene (expanded and unexpanded) Polyurelhane (expanded and unexpanded) PVC (polyvinyl chloride greater than 15 percent plaSlicized. e.g .• coated fabric unsupported film) SAN (slyrene acrylonilrile) SBR (styrene-butadiene rubber) 8101.4.2.3 Group B plastics. Group B plastics are plastic malerials having a heat of combuslion and a burning rate higher than that of ordinary combustibles. but not as high as [hose of Group A plastics. Examples of Group B ptasrics include, but are not limited to, the following: Cellulosics (cellulose acelale. cellulose acelale bUlyrate. ethyl cellulose) Chloroprene rubber Ruoropl.S!ics (ECTFE. ethylene-chlorotrifluoroethylene copolymer; ETFE, elhylene-telrafluoroelhylene copolymer; FEP, fluorinated ethylene-propylene copolymer) Natural rubber (nonexpanded) Nylon (Nylon 6, Nylon 6/6) PVC (polyvinyl chloride greater than 5 percent. but not exceeding 15 percenl plasticized) Silicone rubber 8101.4.2.4 Group C plastics. Group C plastics are plastic malerials which have a heat ofcombustion and a burning rate similar £0 those of ordinary combustibles, Examples of Group C plastics include, but are not limited 10. the fonowing; FluoroplaSlics (PCTFE. polychlorotrifluoroethylene; PTFE. polytelrafluoroethylene) Melamine (melamine fonmaldehyde) Phenol PVC (polyvinyl chloride. rigid or plasticized less than 5 percenl, e.g .• pipe. pipe fiuings) PVDC (polyvinyJidene chloride) PVDF (polyvinylidene fluoride) PVF (polyvinyl fluoride) Urea (urea fonmaldehyde) 8101.4.3 Limited quantities ofGroup i\ plastics in mixed commodities. Figure 810 l.4-A shall be used lOdelermine {he quantity ofGroup A Plastics aHowed to be srored in a package or carton or on a pallet without increasing the commodity dassification. 1-353 8101.5-8101.6.6 , 1994 UNIFORM FIRE COPE S101.5 Designation of High.piled Storage Areas. 8101.5.1 General. High-piled storage areas, and ponions of high-piled storage areas intended for storage ofa different commodity class than adjacent areas, shaH be designed and specifically 􀁤􀁥􀁳􀁩􀁧􀁾􀀠 nated to contain Class r. Class II, Class III, Class IV or high-hazard commodities. The designation ofa high-piled combustible storage area. or portion thereof intended for storage ofa different commodity class, shall be based on the highest hazard commodity class stored except as provided in Section 8!O I.S.2. S101.S.2 Designation based on engineering analysis. The designation ofa high.piled combustible storage area, or portion thereof, is allowed to be based on a lower hazard class than that of the highest class of commodity stored when a limited quantity of the higher hazard commodity has been demonstrated by engineering analysis to be adequately protected by the sprinkler system pro· vided. The engineering analysis analysis shall consider the ability of the sprinkler system to deliver the higher density required by the higher-hazard commodity. The higher density shall be based on the actual storage height of the pile or rack and Ihe minimum allowable design area for sprinkler opera· tion as set forth in the density/area figures provided in U.F.C. Standards 81-1 and 81-2. The contiguous area occupied by higher-hazard commodity shall not exceed 120 square fe.. (I US m2). and additional areas of higher-hazard commodity shall be separated from other such areas by 25 feet (7620 mm) or more. The sprinkler system shall be capable of delivering Ihe higher density over a minimum area of 900 square feet (83.6 m2) for wet pipe systems and 1.200 square reet (III.S m2) for dry pipe systems. The shape ofthe design area shall be in accordance with the Building Code (see U.B.C Standard 9-1). 8101.6 Housekeeping and Maintenance. 8101.6.1 Rack structures. The structural integrity of racks shall be maintained. 8101.6.2 Ignition sources. sources. 8101.6.2.1 General. Clearance from ignition sources shall be provided In accordance with 􀁓􀁥􀁣􀁾􀀠 tion 1109. 8101.6.2.2 Smoking. SmOking shall be prohibited. Approved NO SMOKING signs shall be conspicuously posted. See Section 1109.4. 8101.6.3 Aisle maintenance. When restocking is not being conducted, aisles shall be kept clear of storage, waste material and debris. Fire department access doors, aisles and exil doors shall not be obstructed. During restocking operations using manual slocking methods, a minimum unobstructed aisle width of24 inches (609.6 mm) shall be maintained in 48-inch (1219.2 mm) or smaller aisles. and a minimum unobstructed aisle width of one half of the required aisle width shall be maintained in aisles greater than 48 inches (1219.2 mm). During mechanical stocking operalions, a minimum unobstructed aisle width of 44 inches (1117.6 mm) shall be maintained. See Section 8102.9. 8101.6.4 Pile dimension and height limitations. See Section 8103.3. 8101.6.5 Arrays. See Section 8103.4. 8101.6.6 Flue spaces. See Section 8104.3. 1-354 I 199q UNIFORM FIRE CODE Bl0l.4-A,8102-8102.2 FIGURE Bl01.4-A-MIXED COMMODITIES'·> (See Section 8101.4.3) o 5 10 15 20 25 Percent by Weight of Unexpanded Plastic4 I'This table is intended to determine the commodity classification of a mixed commodity in a package. carton or on a pallet when plastics are involved. 2The following is an example of how (0 apply the !able: A package containing a Class In commodity has 12 petcent Group A expanded plastic by volume. The wClght ofthe unexpanded plastic is 10 percenL This commodity is classIfied as a Class tV commodity. If the weighl or the unexpanded piastic is increased LO 14 percent. the classification changes (0 a high-hazard commodity. 3Percent by volume "" Volume of plastic in pallet load TOlal volume of paller load, including pallet 4Percent by weight '" Weight of plastic in pallet load TOlal weight of pallet load. including paUel SECTION 8102 GENERAL FIRE-PROTECTION AND LIFE-SAFETY FEATURES 8102.1 General. Fire-protection and life-safety features for high-piled storage areas shall be in accordance with Section 8l02, Nationally recognized standards or guidelines. as applicable. are allowed to be used when approved by the chief 8102.2 Separation of High-piled Storage Areas. Portions of buildings that do not meet the requirements of Article 8t for high-piled storage areas shall be separated from 􀁨􀁩􀁧􀁨􀁾􀁰􀁈􀁥􀁤􀀠storage areas by one of the following methods: EXCEPTION: Separation is not required bet\\'ecn accessory areas that (Ire fully protected with automatic sprinkler systems. Accessory areas shan include. but need nOI be limited 10. loading areas, check out areas. restmoms, employee lounges and offices. Fire protection for high-plied storage and smoke and heal venting shall ex:tend a minimum of 15 feet (4572 mm) beyond the high-piled storage area. L A 􀁴􀁷􀁯􀁾􀁨􀁯􀁵􀁲􀀠areawsepa ralion wail bel ween areas not protected with automatic sprinkler systems or 􀁨􀁩􀁧􀁨􀁾􀁰􀁈􀁥􀁤􀀠storage areas in excess of the maxlmum allowabte areas set forth in Table 81 wA, 2. A A 60-foo, (18288 mm) space not used for combustible storage. or 1-355 8102.2-8102.6.4 1994 UNIFORM FIRE CODE 3. A minimum ofa one-hour occupancy separation wall between other sprinklered areas that are not accessory to the high-piled storage area, 8102.3 Fire Sprinklers. Fire sprinkler systems shall be provided in accordance with Sections 8103 and 8104. 8102.4 Fire Detection. When fire detection is required by Table 81-A, an approved automatic fire-detection system shall be installed throughout the high-piled storage area. The system shall be monitored and shall be in accordance with Section 1007, 8102.5 Building Access. 8102.5.1 Access roadways. When building access is required by Table SI-A, access roadways shall be provided to within ISO feet (45.7 mm) of all portions of the exterior walls of buildings used for high-piled storage. EXCEPTION: When access roads cannot be installed due to topography. railways, walerways, nonnego· tiablegrndesorothersimilarconditions.lhe chief is authorized to require additional fire protection as required for special hazards in Section 1001.9. Specifications for fire apparatus access roads shall be in accordance with Section 902,2, 8102,5,2 Access doors. 8102.5.2.1 General. When building access is required by Table SI-A. fire department access doors shall be provided in accordance with Section 8102.5.2. Access doors shall be accessible with· out the use of a ladder. 8102.5.2.2 Number of doors required. One or more access doors shall be provided in each 100 Uneal feel (30 480 mm), or major fraction thereof. of the exterior walls which face required access roadways, 8102.5,2.3 Door size and type. Access doors shall not be less than 3 feet (914 mm) in width and 6 feet 8 inches (2032 mm) in height. Roll-up doors shall not be used unless approved by the chief, 8102.5.2A Locking devices. Only approved locking devices shall be used. 8102.6 Smoke and Heat Removal. 8102.6.1 General. When smoke and heat removal are required by Table S'I-A, smoke and heat vents shall be provided in accordance with Section 8102.6. EXCEPTIONS: I. Whenlhe installation orsmoke orsmoke and heat vems is determined by the chief to be impractlca!, mechanical 􀁳􀁭􀁯􀁫􀁥􀁾􀁲􀁣􀁭􀁯􀁶􀁡􀁬􀀠systems arc allowed lO be provided in accordance Wilh U.EC STandard 81·3. 2. Frozen food storage classified as a Class I or Class It commodi(y is not required to be provided wilh smoke and heat venls or mechanical stnoke removal when protected by an automatic sprinkler system. 8102.6.2 Types of"nts, Smoke and heat vents shall be ofan approved type and shall be operated automatically by activation of. heaHesponsive device rated between 100 and 200"F. (37.8 and 182,2°C.) above estimated ambient temperatures. The heat-responsive device shall be listed and labeled. Smoke and heat vents shall activate fully when [he vent cavity is exposed to a simulated fire or a time/temperature gradient that reaches an air temperature of 500Q F. (260°C.) within five minutes. Smoke and heat vents shalt have the capability of being opened by an approved manual operation. 8102,6,3 Vent dimensions. The effective venting area shaH not be less than 16 square feet (1.49 ml) with no dimension less than 4 feet (1219 mm), excluding ribs or gutters having a total width not exceeding 6 inches (152.4 mm). 8102.6.4 Vent locations, Smoke and heat vents shall be located in accordance with Table 81·B. Vents shaH be located 20 feet (6096 mm) or more from lines ofadj.ce", properties and 10 feet (3048 mm) or more from occupancy separation waHs separating other high-pUed storage areas. Vents shall be uniformly located within the roof area above high-piled storage areas. 1-356 1994 UNIFORM FIRE CODE 8102.7--8102.10 8102.7 Curtain Boards. 8102.7.1 General. When curtain boards are required by Table BI-A. curtain boards shall be pro· vided in accordance with Section 8102.7. 8102.7.2 Construction. Curtain boards shall be constructed of sheet metal. lath and plaster. gyp. sum wallboard. or other approved materials which provide equivalent performance that will resist the passage of smoke. Joints and connections shall be smoke tight. 8102.7.3 Location and depth. The location and depth of curtain boards shall be in accordance with Table 81·B. 8102.8 Hose Stations and Hose Connections. 8102.8.1 Small bose stations. When small hose valves and stations are required by Table 81·A. approved Ith-inch (38.1 mm) hose valves shall be provided at approved locations. When reqUired by the chief. hose, nozzles. hose racks. and cabinets or covers shali be provided. See U.F.C. Stand· ards 81-1 and 81-2. 8102.8.2 Fire department hose connections. When exit passageways are required by the build· ing code for egress, a Class I standpipe system shall be provided in accordance with the Building Code. See U.B.C. Standard 9·2. 8102.9 Aisles. 8102.9.1 General. Aisles providing access [0 exits and fire department access doors shall be prow vided in high·piled storage areas exceeding 500squ.re feel (46.45 m2) in .ccordance wirh Section 8102.9. For aisles separating storage piles or racks, see also U.F.e. Standards 81-1 and 81-2 and Article 88. EXCEPTION: Where aisles are precluded by rack storage systems. alternate methods of access and protecllon are allowed when approved by the chief. 8102.9.2 Width. 8102.9.2.1 General. Aisle width shall be in accordance with Section 8102.9.2. EXCEPTIONS: L Cross aisles used only for employee access between aisles shall be 24 inches (609.6 mm) or more in width, 2. Aisles separating shelves classified as shelf stOrage shall be 30 inches (762 mm) or more in width. 8102.9.2.2 Sprinklered buildings. Aisles in sprinklered buildings shall be 44 inches 0117.6 mm) or more in width. Aisles shall be 96 inches (2438.4 mm) or more in width in high·piled storage areas exceeding 2,500 square feet (232.26 m2) in area and designated to contain 􀁨􀁩􀁧􀁨􀁾􀁨􀁡􀁺􀁡􀁲􀁤􀀠commodities, Aisles shall be96 inches (2438.4 mm) or more in width in public accessible areas where mechanical stocking rnerhods are used. 8102.9.2.3 Nonsprinklered buildings. Aisles in nonsprinklered buildings shall be 96 inches (2438.4 mm) or more in width, 8102.9.3 Clear height. The required aisle wid,hshall extend from floor to ceiling. Rackstruclurnl supports and catwalks are allowed to cross aisles at a heighr 6 feet 8 inches (2032 mm) or more above the level of the finished floor. provided that such supports do not interfere with fire 􀁤􀁥􀁰􀁡􀁲􀁴􀁾􀀠 ment hose stream trajectory. 8102.9.4 Dead ends. Dead end aisles shall be in accordance with the Building Cnde (see U.B .C. Chapter 10), 8102.10 Portable Fire Extinguishers. Portable fire extinguishers shall be provided in accord· ance with U.F.e. Standard 10·1. 1-357 8103-8104.3.2 1994 UNIFORM FIRE CODE SECTION 8103 -SOLID-PILED AND SHELF STORAGE 8103.1 General. Shelf storage and storage in solid piles. solid piles on pallets and binbox storage in binboxes not exceeding 5 feet (1524 mm) in any dimension shall be in accordance with Sections 8102 and 8103. 8103.2 Fire Protection. 8103.2.1 General. When fire sprinklers are required by Thble gl-A. an approved automatic fire sprinkler system shall be installed. The design and installation of the automatic ftre sprinkler system and other applicable ftre protection shall be in accordance with the Building Code (see U.B.C. Standard 9-1) and U.F.C. Standard 81-1. 8103.2.2 Shelf storage. Shelf storage greater than 12 feet (3658 mm) but less than 15 feet in height shall be in accordance with the fire-protection requirements set forth in U.F.c. Standard 81-1. Shelf storage 15 feet (4572 mm) or more in height shall be prole<:ted in an approved manner with special flre protection, such as in-rack sprinklers. 8103.3 Pile Dimension and and Height Limitations. Pile dimensions, the maximum permissible storage height and pile volume shall be in accordance with Table 81-A. 8103.4 Array. When a fire sprinkler system design utilizes protection based on a closed array. army clearances shall be provided and maintained as specifled by the standard used. SECTION 8104 RACK STORAGE 8104.1 General. Rack storage shall be in accordance with Sections 8102 and 8104. Binboxes exceeding 5 feet (1524 mm) in any dimension shall be regulated as rack storage. 8104.2 Fire Protection. 8104.2.1 General. When fire sprinklers are required by Table 81-A, an approved automatic fire sprinkler system shall be installed, The design and installation of the automatic fire sprinkler system and other applicable file protection shan be in accordance with the Building Cede (see U.B.C. Standard 9-1) and U.F.c. Standard 81-2. 8104.2.2 Plastic pallets and shelves. Storage on plastic pallets or plastic shelves shall be protected by approved specially engineered flre-protection systems, 8104.2.3 Racks with solid shelving. 8104.2.3.1 General. Racks with solid shelving having an area greater than 32 square feet (2.97 m2), measured between approved flue spaces at all four edges of the shelf, shall be in accordance with Section 8104.2.3. EXCEPTlON: Racks with mesh. grated, sianed or similarshelvcs having unironn openings not more Ihan 6 inches (152.4 mm) apart. comprising at leasl50 percent of overall shelf area, and with approved flue spaces. are allowed to be treated as racks without solid sbelves. 8104.2.3.2 Fire protection. Fire protection for racks with solid shelving shall be in accordance with the requirements for racks with solid shelving set forth in U.F.C. Standard 8l-2 or other nationally recognized standards. See Article 90, Standard f. I. I. 8104.3 Flue Spaces, 8104.3.1 General. Flue spaces shall be provided in accordance with Section 8104.3. Required flue spaces shall be maintained. 8104.3.2 Transverse flues. Racks that are not protected with an approved tn-racle sprinkler system shall have nominal3-inch (76.2 mm) transverse flue spaces provided between loads or at rack uprights. Random variation in width or in vertical alignment is allowed, provided the configuration does not obstruct water penetration. 1-358 1994 UNIFORM FIRE CODE 8104.3.:>-8104.5.2 8104.3.3 Longitudinall1ues. Six·inch (152.4 mm) longitudinall1ue spaces shall be provided in double and multirow racks. EXCEPTION: Longitudinal flue spaces in 􀁤􀁯􀁵􀁢􀁬􀁥􀁾􀁲􀁯􀁷􀀠rack!> not exceeding 25 feel (7620 mm) without solid shelving that are provided with 􀀶􀁾􀁩􀁮􀀨􀁨􀀠(IS2,4 mm) lran5verse flue spaces. 8104.3.4 ESFR sprinklers. Longitudinal flue spacing shall be provided in rack configurations that are protected by early suppression· fast response (ESFR) sprinklers. 8104.4 Column Protection. Steel building columns shall be protected in accordance with v.F.e. Standard 81·2. 8104.5 ExtTahlgh-rack Storage Systems. 8104.5.1 Required approvals. Approval of the chief shall be obtained prior to installing extra· high·rack combustible storage. 8104.5.2 Fire protection. Buildings with extrahigh.rack combustible storage shall be protected with a specially engineered automatic sprinkler syslem. Extrahigh-rack combustible s(orage shall be provided with additional special fire protection, such as separation from other buildings and additional 􀁢􀁵􀁩􀁬􀁴􀁾􀁩􀁮􀀠􀁦􀁩􀁲􀁥􀁾􀁰􀁲 􀁯􀁴􀁥􀁣􀁴􀁩􀁯􀁮􀀠features and fire department access, when required by the chief. 1-359 " TABLE 81-A-GENERAL FIRE-PROTECTION AND LlFE·SAFETY REQUIREMENTS i 1------COMMODITY CLASS , LJ'\1 High huznrd SIZE Of HIGH,PILED SlOFIAGE AIlEA1 (1lQ. fl.) !Su Slcllan 8102.2) ! x 0.0929 for rot "a....uII .. "",,"'I 􀁏􀁾500 : 􀁾􀀺􀀺􀀠 501·2,500 I .,-, ..-, 2,SOI-12.000 Public accessible f-2.501-12,000 Nonpublic 􀁾􀁣􀁣􀁥􀁳􀁳􀁩􀁢􀁬􀁥􀀠 I----_(Opt;o. I) 2,50 I -1 2,000 Nonpubllc accessible (Option 2) 12,001-20,000 20.00 1-500.000 Greater than 500;aoos 0·500 501-2.500 Public accessible 501-2,500 Nonpublic aL'Cessible Yes NR Yes Yes Yes NR Yes +-"'N""R---j-NR.----I-N R 􀁎􀁾􀀠 Yes 􀁾􀀭􀀭 􀁹􀁾􀁳􀀠 ------------􀀭􀁾􀀠 Ves Yes NR Yes Yes Ves NR Yes Yes Ve' NR Ye' Ye' Yes NR NR' NR NRC! NR NR" NR NR' -NR6 NR I NRJ SCUD·PllED STORAGE, SHELF STORAGE ANO PALLETtZED STORAGE 􀀨􀁾􀁥􀀠􀁾􀁤􀁬􀁬􀁬􀁮􀀠81M.3} MaXlmllm Maximum f'ermls:sibla PliO' Dlmtn-􀁓􀁬􀁴􀁬􀁾􀀱􀀠 Maximum 1'11& I """1'.1 _ H",M In.J Yolum. itl!. fl.) x3(J48lnrmm x OJtZaflor iri3" NR NR NR 100 40 100.000 100 40 400.000 NR 100 40 -400.000 ---Ye, 100 I 301 200,000 ! Yes 100 40 400.000 Yes 100 40 400,000 Yes 100 40 400.000 NR 50 NR NR NR 50 30 75,000 50----30----------NR 75.000 (Opt;o. I) --I SOI·2,SOiI NR 􀀭􀀭􀀭􀀭􀁹􀁥􀁳􀁾􀁟􀀱􀀭􀀭􀀭􀀭􀁹􀁥􀀻􀁾􀀭􀀭􀀭􀀭 􀁹􀁾􀁳􀀠 Yes -+-----:; --r--sor--io-r--50,QOO Nonpublic accessible 1----__ IOpoon 2) 2,501·300,000 ¥c;; NR Yes +-Ycs--Yes Yes. 50 􀀮􀁾􀀮􀀭 --t-----7s.ooo 􀁟􀁾􀀠300,00 1.500.000&:';-I YeliNR Yes Yes 􀁾􀀠 􀁙􀁥􀁾􀀠 Yes 50 30 75,000 Nk = Nvl required, 'The size or Ihe high-piled slornge area 10 be considered when ul>ing this 1;lblc shlil/mciude Ihe high·piled storage area and all portions oflhe building nO! separated (rom Ihe high-piled storage area in accordance with Section 8l02.2. 2For aisles. see Section 8102.9. .3Curtllil'l hoards shuH be lOstnlled as required by the Building Code. Sec U.B.C. Section 906. 􀁾􀀠 ;i. 􀁾􀀠 I 􀁾􀀠 ::!l 1\1 8 o m 􀁾􀀠 4Piles shall be separaled by aisle... complying with Section 8102.9. 5For.storage in 􀁥􀁾􀁣􀁥􀁳􀁳􀀬 of the height tndicated, spedal fire protection shall be provided in accordance with footnote 8 when required by the chief. See also Ankles 79 and 88 for speclallimilalions for flammable and combuslible liquids and aerosols. 6Section 902.2 shall apply for fire apparatus access, 7For storage exceeding 30 feel (914 mm) in height. Option I shall be used, 8Special fire-proteclion provisions SUCh as, but nollimlted to, (ire protection of exposed steel columns; increased sprinkler density; additional in-rack sprinklers, without associated reductions in ceiling sprinkler density; or additional fire department hose connections shall be provided when required by the chief. 9High-piled storage are3sshall nOot ex.ceed SQO,OOOsquare feel (46 451.5 m2). A Iwo·hour area separation wall shall be used to divide high-piled storage exceeding 500,000 square feet (46 451.5 m2) in area. TABLE 8Hl-REQUIREMENTS FOR CURTAIN BOARDS AND SMOKE VENTING' (See Secllons 8102.6.4 and 8102.7.3) 􀁾􀀠 􀁾􀀠 -§i 􀁾􀀠 !ll Jl ::0 III 􀁾􀀠 _ ... . CDMMODITY CLASSIFICilTION I·IV , (Option I) c----.. I (OpHtioVn 2) 'I 􀁾􀀠 I HIgh hazard cCOPdQnl) 􀁈􀁾􀁨􀀠hazard ( plion 2) . 􀁾􀁅􀁓􀁉􀁇􀁦􀁴􀁁􀁔􀁅􀁏􀀠STORAGE I􀁾􀀠 􀁾􀂷􀁲􀁗􀁉􀁍􀁕􀁍􀁁􀁁􀁅􀁁􀁆􀁏 􀁒􀁾􀁏􀀠J􀁾􀁾􀀭 􀁍􀁁􀁘􀁉􀁍􀁩􀁊􀀻􀁉􀁦􀁓􀁐􀁁􀁣􀁩􀁩􀁩􀁾􀁍􀁁􀁘􀁉􀁍􀁕􀁍􀀠DISTANCE 10 CURTAIN aOAllD BY CURTAIN aoARD OF VENT CEllffilS VENTS: FROM WAll OR HEIGHT (ft.j I O:tmfilt.J (Iq. _ft •.} VEHT Al'lEA10 FLODR (It) ____ 􀁾􀁾􀁦􀀡􀁔􀁾􀁉􀁾􀀠BOARDS' 􀁾􀀢􀀮􀀩􀀠 x 3048 101 mm ){ UI929 􀁉􀁾􀁲􀁾􀀠 AREA RA1!O x3M11lot mm 20 or less 6 10.000 1,100 100 60 over 20·40 6 8,000 1:15 Joo 55 20 or less 4 3.000 1:75 100 55 over 20-40 4 3.000 1:50 100 50 20 or less 6 6,000 1:50 100 50 over 20-30 6 6,000 1:40 90 45 20 or less 4 4,000 1:50 100 50 over 20-30 4 2,000 J:30 75 40 IFor rack !;torage heights In 􀁥􀁸􀁣􀁥􀀮􀁾􀁳􀁯􀁦􀁬􀁨􀁯􀁳􀁥􀀠Indlcaled, see Secllon 8104.5. Forsoltd-pl1ed storage heights In ex.cessof thOl>e mdicated, an approved engineered design shall be used. 2When curtain boards are provided in buildings equipped with early 􀀵􀁵􀁰􀁰􀁲􀁥􀀡􀁜􀁳􀁩􀁯􀁮􀁾􀁦􀁡􀀮􀁳􀀱􀀠response sprinklers, !hecunain boards shall he located only at Iheperimetersorsprinkler systems. 3The distance specified is the maximum distance from any vent in a particular curtained area 10 walls Of curtain boards which fonn fhe perimeler of the curtained area. s t i" 􀁾􀀠 "' ® 10. Sec. 5-13.2 is revised as follows: Sec. 5-13.2. Sprinklers shall be installed at the ceiling and beneath shelves in single-, double-and multiple-row racks with solid shelves, as set forth in U.F.e. Section SIA02 (c), in accordance with Table No. 5-13.2. Design curves for 􀁣􀁯􀁭􀁢􀁩􀁮􀁾􀁤􀀠ceiling and in-rack sprinklers shall be used with this type of storage configuration. TABLE NO. 5·13.2-SPRINKLER REQUIREMENTS FOR SOLID SHELF STORAGE COMMODITY CLASS STORAGE HEIGHT (It.) SPRINKLERS REQUIRED IN-RACK Shell Area 32-50 Square Feet Shell Area Greater Than 50 Square Feet Over 12-20 I level t Every tier of storage I·IV Over 20-25 2 levels2 Every tier of storage Over 25 J , High hazard Over 12 Every tier of storage Every tier of !>torage 'Locate one level of in-rack sprinklers at a height of one halflO two thirds oflhe rack height. 2Locate one level of in-rack sprinklers at a height of one fourth to one third of the rack height and a second level at two thirds to three fourths of the rack height. 3PrOlect in accordance with nationally recognized standards. See U.F.C. Section 2.304 (b). Standard No. f.I.I. 11. Sec. 6-1 is revised by substituting the phrase "the Building Code. See U.B.c. Standard No. 38-1" for the phrase "Installation of Sprinkler Systems, NFPA 13." 12. Sec. 7-1 is revised by substituting the phrase "the Building Code. See U.B.e. Standard No. 38-1" for the phrase "Installation of Sprinkler Systems, NFPA 13." 13_ Sec_ 8-1.4, Exception 4, is revised by substituting the phrase "the Building Code. See U.B.e. Standard No. 38-1" for the phrase "NFPA 13, Standard for Installation of Sprinkler Systems." 14. Sec. 8-1.5 is revised by substituting the phrase "the Building Code. See U.B.C. Standard No_ 3S-I" for the phrase "NFPA 13, Standard for Installation of Sprinkler Systems." 15. Sec. 9-1.2 is revised by substituting the phrase "the Building Code_ See U_B.e. Standard No. 38-1" for the phrase "NFPA 13, Installation of Sprinkler Systems." 16_ Sec. 10-2_3 is revised by substituting the phrase "the Building Code. See U.B.C. Standard No. 38·1" for the phrase "NFPA 13, In· stallation of Sprinkler Systems." 17. Chapters 11, 12 and 13 are deleted. Part II Reproduced with pennission from the Standard for Rack Storage of Materials, NFPA 231C, copyright 1991, National Fire Protection Association, One Batterymarch Park, Quincy. Massachusetts 02269. Persons desiring to reprint in whole or part any ponion of the Standard for Rack Storage of Materials, NFPA 23IC-1991. must secure pemlissian from the National Fire Protection Association. The followine is not necessarily the latest revision used by NFPA. If the reader desires to compare that version, the same is available ('rom NFPA. Also: Add a V.F.e. standard as follows: UNIFORM FIRE CODE STANDARD NO. 81-3 MECHANICAL SMOKE-REMOVAL SYSTEMS See Section 81.206 (a), Uniform Fire Code Scope Sec. 81.101. Mechanical smoke-rcmoval svstems designed to remove smoke from high-piled storag.e areas after'a [lrc is 􀁥􀁘􀁬􀁩􀁮􀁾􀁧􀁵􀁩􀁳􀁨􀁥􀁤􀀠 and assislthe fire department during suppression opcrations shall be in accordance with this standard. When mechanical smoke-removal systems are provided, curtain boards shall be provided as required by U.F.c. Section 81.207. System Capacity Sec. 81.102. The volume of mechanical ventilation required shall be detennined by the following fomlUla: I'=Ax300 WHERE: V volume of mechanical ventilation required, in cubic feet per minUle. A area of roof vents required by Table No. SI-B, in square feel. Supply Air Sec. 81.103. Supply air forexhausl fans shall be provided at or near the noar level and shall be sized to provide a minimum of 50 percent of required el(hausL Openings for supply air shall be uniformly distributed around the periphery of the area served. Fans Sec 81.104. Fans shaH be in accordance with the following: (a) The individual capacity ofa fan shall not el(ceed 30,OOOcubic feel per minute; (b) One or more exhaust fans shall be provided in each curtained area, and when more than one el(hausl fan is provided in a curtained area. the fans shall shall be unifonnly spaced within the curtained area. The distance between fans within a curtained area shall not el(ceed 100 feet; (c) Wiring and smoke· removal fan units shall be thennally protected in a manner that will provide continued operation for not less than 15 minutes while exposed [0 a temperature of 1,000°F.; and EXCEPTION: Wiring and electrical equipment installed on Ihe exterior of the building. (eI) Controls for mechanical smoke-removal systems shall be as follows: I. On combination comfort air-handling and smoke-removal systems. and on independent comfort air-handling systems, fans shall be controlled to shut down in accordance with the automatic shutoff requiremems of the Mechanieal Code or by activation of automatic extinguishing or detection systems; 2. Electrical service to the smoke-removal systems shall be con· m!cted on the line side of the main electrical disconnect; and 3. The smoke-removal system shall be provided with a fire department control panel located in an approved location location and clearly identitied. The control panel room shall be protected by not less than a onehour occupancy separation in accordance with the Building Code. The room shall be accessible from [he exterior of the building. Automatic sprinkler protection shall be provided in the control room. Reason: The revisions were 100 comprehensive to be fully reviewed at the hearing, Staff Note: Tile Code Del'elopmelH Commiltee directed sraffto prim the di5cll'I'I"OI'{I/(/.\' I'('I'i.\'l!d 1·/!I'.tiOIl ill Ihe Annual Report of the Code Development Committee lOal/ou' clUJllenges 10 he hased 011 ,he revised version. Following the hearing, siaffme' \\'i,II 'he 1)1"01)0IleIll5 10 l'e50/I'e additional outstallding issues. As cl reslIll of 􀁉􀁬􀁬􀁩􀀮􀁾􀀠 􀁭􀁥􀁥􀁬􀁩􀁬􀁬􀀮􀁾􀀬􀀠I/Umerou5 additional revisiOl/s beyond Ihose suhmilled {II ,lie IIearillg "m'e heell made. Tile I·U.fioll primed hereil! liaS heen proI'hied lIy Ille 1'I'OI)olIell/.( to I'{·.whe Ihe C(lncems presented allhe heari/l!: and la IIIcorporalt' xwff COlllmelll.f. Proponent's Reason Substantiating the Revised Proposal: This updated version of th.: Article 81 rewrite is bas.:d on the activity of the Article 81 rewrite suhcmnlllillee that was fomled by the Southern California Fire Prevention Officers Unironn Fire Code Commillee. This subcommiuee has been in operation fur two ycars and has commiued oVer 30 eight-hour days of meetings. plus countless hours of individu:ll rcsearch. to assemble this rewrite of Article 81. 􀁔􀁨􀁩􀁾􀀠commillee was made up mainly of fire marshals and fire protection engineers from fire department!> around the United Slates. Other contributing members included fire protection consultants. representatives from Faetory Mutual Engineering.. fire sprinkler contractor.>. representatives from the smoke and heat V':Tlt industry. and fire sprinkler manufacturers. The purpose of the rewrite is 10 update the requirements for high-piled combustible slordge to reflect more current fire-protection philosophy. The changes that have been made to the current arucles are outlined below, Overall. Article 81 has hcen rewnllen to include three divisions. Division I includes administrative and general requirements. Division II includes general firc-and life-safcty provisions and directly correlates with Table No. 81-A, Division 111 includes specific requirements for solid-pile and similar storage, and Division IV 􀁩􀁮􀁣􀁬􀁵􀁤􀁣􀁾􀀠specific requirem.:nts for raek and similar storage. The 94 I article was divided inlo four divisions to make the code more user friendly and make the application of the code by the fire inspector an easier fask. Division I. For consistency wilh code formal. all general definitions will be located in Article 9. Many 􀁾􀁥􀁷􀀠definitions have been added. These include "array"; "array, closed"; "'binbox"; "curtain board"; 􀀢􀁥􀁸􀁦􀁲􀁡􀁨􀁩􀁧􀁨􀁾 􀁲􀁡􀁣􀁫􀀠combustible storage"; "shelf􀁳􀁬􀁯􀁲􀁡􀁧􀁥􀀢􀀻􀁾􀀢􀁳􀁯􀁬􀁩􀁤 shelving"; and"transverse flue space." The curremdefinition of solid shelving !sone of the major areas ofenforcen"!enl problems with Ankle 81. The commiuce agreed that tile 1991 Unifonn Fire Code Standard No. 􀀸􀀱􀁾􀀲􀀠allows solid shelves that are much tOO large. For example, assuming standard 8M fool rack uprights, and a rackdeplh of4 feet. 􀁕􀁮􀁩􀁦􀁾􀁮􀁮􀀠􀁾􀀻􀁩􀁲􀁣􀀠 Code Standard No.8 i -2 would allow double-row rdcks Jess than 25 feel 10 helght to have soUd shelves 64 square fee! in area (rack width times distance belween uprights timcs tWi,) for each side of the raek. 4 feet x8 feel x 2;::: 64 square feel) Note that longitudinal flue spaces are Il{)[ required for doub!ewrow racks under 25 feet in 􀁾􀁩􀁧􀁨􀁴􀀠Factory Mutl!al. Engineering Loss Prevention Data Sheet 􀀸􀀭􀁾􀀳􀀠 defines sohd shelves as shelves having an area greater than 20 square fecL Dlf· ferent protection requirements are provided based on 20 square feet. 20 to 5.0 square feet. and over 50 square feeL The commiuee evaluated these twO poSLw lions and used engineering judgment to conclude thaI solid shelves greater than 32 squate feet create a fire hazard significant enough to require rack sprinkler protection, This decision is bascd on research that showed no conclusive fire testing has been conducted to clarify [his issue. Factory Mutual Engineering's posilion is based on judgment that greater Ihan one panet (approx:im3Iely 20 square feet) couid obstruct sprinkler water penetration through a rack.l1le 􀁰􀁯􀁳􀁩􀁾􀀠 tion taken by the 1991 Uniform Fire Code Standatrl No.8 I􀁾􀀲􀀠is also based on engineering judgment. Section B-5-13.2 states thai "these tcslslsolid soclving fire tests} did not yield sufficient infonnation [0 develop a comprehensive protection standard for solidshelfracks. Items such as increased ceiling density, use of bulkheads, other configurations of sprinklers in racks, and limitation of shelf length and width require consideration," . Submittal requirements have been increased to require the permil applicant for 􀁨􀁩􀁧􀁨􀁾􀁰􀁩􀁬􀁥􀁤 storage buildings to provide specific information thai is needed for the fire depanmem to ptovlde for proper regulalion. In Section 8Lim (b), required infonnation includes 14 different informational items [hat are needed by the fire department so that proper determination for fire protecrion can be made, Classifications of commodities were updtned. A tremendous amount of research and effon went into this process. Individuals from throughout the United States contribuled to this effort. The Jist provided renects the vcry late:>! results of researeh and technology. At the request of the Code Development CommjUee. descriptions of Groups A. B and C plastics have been added in Seclion 81.104 (b). Accompanying the descriptions are lists of common plastics by group classificatlon. The Code Development Commilteedecided Ihat 􀁴􀁨􀁥􀁾􀁥􀁤􀁥􀁳􀁣􀁲􀁩􀁰􀁬􀁩􀁯􀁮� �􀀠were needed by a fire inspector enforcing the Uniform Fire CQde. The elassification ofpvc. based on Ihe amOUIHS of piasticizer, has been added to the code. TItis was based on research done with members of the NFPA 231 commiuee. The age-old problem of classifying mix.ed commodities has been addressed in Section 81.104. The amount of unex.panded and expanded Group A plastics which may be allowed in a package. canon or pallet load without increasing rhecommodity c1a$$ificaw tion is found in Figure No. 81. 104-A. an adaptation ofFactory Mutual Engineetiog and Industrial Ri$k Insurers standards, Onee the commodity classification forthe box.. carton or pallet load is delermined, Section 81. t04 (c) provides guid· anee for how much of a higher-hazard commodity is allowed in a given prodUCI mix without increasing the commodity Classification and the fire-protection requirement$. The new Anicle 81 also introduces a neWcort(;epl of designating the $Iotage area to irnlicate the commodity class mat the :lrea was designed for, Nonnatly. this will correspond 10 the highesl eommodilY class slored, bUI Section 81.105 (b} aHows small quantities of higher-hazard commodity ohhesprin!<.Iersystem to deliver blgh enough waterdcnsity from the finu sprinklers openu· ing to meet the required density for controlling the small quamity of higherhazard commoohy. The amolJnt oftbe higher·hazard commodify allowed mUSl be detennined by an engineering analysis. 'fbI!.; analysis must consider the following two principles: L It is generally believed that the most impenant faClor in protecting a {;om· modity is the sprinkler density. The higherthe.denlpecifictl demmy over a $pecified operating area, the 􀁮􀁾􀁭􀁢􀁥􀁲 of 􀁳􀁰􀁾􀁭􀁫􀁬􀁣􀁲􀁳􀀠which can opentte at a hIgher den$ity can be used 􀁴􀁯􀁤􀁥􀀨􀁃􀁲􀁾􀁭􀁮􀁥 􀁴􀁨􀁥􀁱􀁵􀁡􀁮􀁬􀁬􀁬􀁾􀁏􀁦a 􀁨􀁩􀁧􀁨􀁣􀁲􀁣􀁬􀁡􀁳􀁳􀁣� �􀁭􀁭􀁯􀁤􀁾􀀠 ity which ean be stored with a lowcr elass commodity. Hydraulic calculations must be ptOvi?ed whU;h verifythc: abililyofthe sprin. kler system to provide !his higbe: density, SCCllon 􀁾􀀱􀀮􀀱􀀰􀀵􀀠(b) provide:; further safety factors hy limiting the maximum area oftbe blgher.hazardcommodity 10 ($J 120 square feel in anycomiguous area. Use of this method will allow lhe 􀁪􀁮􀁳􀁰􀁥􀁣􀁾􀀠 lor or plan checker 10 accurately timil and proleci mixed commodity storage. Requirements fot aisle maintenance, ignrrioncontrol, smoking areas and porlable fireex!inguishers have been provided in acon:;olidated seClion for mainrenance, Seetion 8 1.106, Also. the requirements for evacuation plans in 􀁰􀁵􀁢􀁴􀁩􀁣􀁾􀁯􀁣􀁣􀁵􀁰􀁩􀁥􀁤􀀠warebouses have been added based on the fire chief's discretion, depending on the size and risk of the building in question, These are in Section 81.103 (c). Division II, A new Division it has been created to set forth the general fireand tife-safely requiremcots. The sections in Division n track dosely wich requirements in Table No, &l-A. Division iladdresses many major issues.. For example. problems with aisles have been resolved, and the size and width of aisles based on thedifferem standard requirements ofthe Uniform Building Code have been corrected, Requirements for small hoseconneclions have been maintained. The requirements for small hose 00 the hose connections is stililef! to Ihe discrelion of the fire chief. In very large warehouses where travel distances to exits would exceed the ailowableoode limits, exit passageways would be required. The new Section S1.208 (b) would require a Clas$ I standpipe. which complies with Unifonn Building Code Standard No. 3&-2. 10 be installed in these cases. Requirements for regulating industrial trucl";$ and battery charges have been placed in Ankle 11 so thal they apply to all cases where industrial trucks are used in buildings. Ventilation requirements are located in Set:iions 81.206 and SL207 for improved organization. The ventilation topic was the portion ofanide on exiting which Ihe proponent comminee fetl needed the most work. The basis for and documentation to suppon the use of smoke and heat vcnlS and curtain boards in sprinklered bulldings is an 􀁡􀁧􀁥􀁾􀁯􀁬􀁤􀀠que$tion which has generated more disagreemenlsamong fire·protection profe..<;-sionals than any other high-piled 􀁦􀁩􀁲􀁥􀂷􀁰􀁲􀁯􀁬􀁥􀁣􀁾􀀠 lion issue. The reason for this problem is the lack of full-scale fire testing using smoke and heat vents and curtain boards;, None of the current NFPA or Factory Mutual Engineering lests, which are the primary basi$ for all current fire-proteclion slandarris. incorporated smoke and heal vents and draft curtains in thc Ie..<;:ting process. ThU$. Onc's position on this issue IS probabty based on insight gained from reaiwlife lire experience. theoretical evaluation or speculation, Two imponafil questions ncetled to be addressed: I. Do smoke and heat 􀁶􀁥􀁭􀁾􀀠affect automatic fire sprinkler aClivation times? 2. Are smoke and heal vcnts beneficial for manunl firefighling. and when is IheOplttllUm lime for the smQke and heal vents to activme in relation to fire sprinkler activation" To answef 􀁉􀁨􀁥􀁳􀁥􀁱􀁵􀁥􀁾􀁬􀁩􀁯􀁮􀁳􀀠and hopefully pUlthis issue 10 rest once and for all. a 􀁉􀁗􀁯􀁾􀁰􀁡􀁲􀁴􀀠program 􀁷􀁡􀁾􀀠establishe d. First, documentation of all existing testing in this area was compiled and analyzed. Next. testing and researeh currently underway was ex.amined. The proponent eommiuee hoped Ihat by looking at the research in nn analYllcal manner. the tllyth$ and misconceptions could be 􀀵􀁥􀁰􀁡􀁾􀀠 rated from the science and engineering, and a logieal conclusion could be reached. The proponent contminee reaehed Ihe following conclusions: I, All completed research iudkates lhat smoke and beal vents do not have a detrimental affect on automatic sprinkler 􀁯􀁰􀁥􀁲􀁡􀁬􀁩􀁯􀁮􀁾􀀮� �Smoke and heat vents do reduce ceiling temperJ.tures and improve visibililY for manual firefighting, 2. The !>l1loke and heat 􀁶􀁥􀁮􀁴􀁾􀀠should probably activate prior to llc\ivation of the firc sprinkler:; 10 reduce lhe thickness of the upper layer and. tllus.lhe potential for smoke·logging of the building. 3. Curtnin boards provide no benefit in a sprinklered huilding and could adversely affect sprinkler aCII\'ation and 􀁩􀁮􀁣􀁲􀁥􀁡􀁾􀁥􀀠the likelihood of 􀁳􀁭􀁯􀁫􀁥􀁾􀁬􀁯􀁧􀁾􀀠 ging. Ventilation 􀁲􀁥􀁱􀁵􀁩􀁲􀁥􀁭􀁥􀁭􀁾􀀠proposed in 􀁻􀁨􀁩􀁾􀀠rewrite were written with these 􀁴􀀺􀁯􀁮􀁾􀀠 elusions in mind. Venting mti0s have been revised decision. Tn the 197! edition of the Uniform Fire emil', Anide 35 was imroduced for high-piled combUlaible storllg('. Requirements for smoke and heal vemsand curwin 􀁨􀁯􀁡􀁲􀁤􀁾􀀠were esmblisbcd for all buildings l'Omaining 􀁨􀁩􀁧􀁢􀁾􀁰􀁩􀁬􀁥􀁤 􀀠Slornge. regardlClis of automatl(; fire protection. Section 35.107 staled that "draft curtains shall be provided to limit (he ::1f('3 of sprinkler opemtion and 10 aid [he opermion ofroof vents, ,. No fire testing or research was done allhallime to justify Ihis 􀁰􀁯􀁳􀁩􀁾􀀠 tion. Articie 35 remained unchanged in the 1973 and 1976 edilions. A majorrewrile of Artide35, which was later renamed Article 8 I, was undertaken forthe 1979 edition oflhe UnifoJm Fire Code. Researehconducted during this rewrite indicated that a mechanical smoke-removal system was preferred and lhat smoke and heat vents and eunain boards were not required in buildings protected by an approved fire-extinguishing system as stated in Seetion g1.107 (a). Smoke and heat vents and curtain boards were also not required in fully sprinklered buildings in the 1982 edition of the Uniform Fire Code. In the 1985 edilJOn, the Uniform Fire Code again changed the smoke and heat vent and draft curtain requirements. Since the 1985 edition, the Uniform Fire Code has required either smoke and heat vents and draft curmins or mechanical smoke removal and draft curtains in buildings used for high-piled storage, regardless of whether the the building was sprinklerw, No new research or fire testing was done to suppon this change hl position. The most well-known and widely distributed testing on smoke and heat vents was work done by the Factory Mutual Researeh Corpol'arion in lis. Rhode Island tes.ting facility in 1974. Factory Mutual's conelusion was that smoke and heat vents were detrimental to automatic fire sprinkler operation and, thus, should nOI be insta-Ued in sprinklered buifdings. Unfonunarely. what is not commonly known is thal. due to the constraints of the Factory Mutual testing facility, these tests had no similarity to real-Wry S}'!tem: 􀁗􀁾􀁴􀀠 Fig. No. Array Flllci. None None 􀁎􀁯􀁮􀁾􀀠 .'102 gpm 9'12 gpm Commodhy; P,E. Boulrs Stonge Height: 18 ft Clear Space: 10 f[ 􀁓􀁴􀀮􀁡􀁢􀁬􀁾􀀯􀁕 􀁮􀁳􀁴􀀮􀁴􀁢􀁬􀁾􀀺􀀠Stable Open/ClMed Array: Open 􀁗􀁾􀀯􀁄􀁲􀁹􀀠System: Wet Clear-Density Array Density D,y Dem",y • nce rea Fact. rea'Pmalty 􀁎􀁏􀁬􀁦􀁴􀁬􀁾􀀠 Fact. (Adj.1 (Adj.): \.26 0.86 756 None 650gpm 0.61 2.3 2.645 None None 1,6U gpm Commodity: P.E, Botdts Storage Height: 24 ft Clear Spa«: 4 fl Stable/Unuable: Stable Open/Cloeed Array: Open Wet/Dry 􀁓􀁹􀀵􀁵􀁾􀁭􀀺􀀠Wet However, sometimes storage height is 24 ft high with 􀀴􀁾􀁦􀁴􀀠clearance. The demand for 20-ft high storage and 11h·ft to 4'/2-ft clearance was: Initial demand: 0.9 gpm/f,' over 600 ft' Secondary demand: 0.65 gpmlft' over 1,150 ft'. However. since the clearance factor for increasing the area is going to be small and a final area of at least 2.000 ft"l is needed, it is decided to pkk a density for the 􀁳􀁥􀁣􀁯􀁮􀁤􀁾􀀠 ary poim that would create an area demand equal to or closer to the 2,000 ftil area. From Figure 7-2.2(c). 'he demand for 20-f' high storage and P/2-ft to 4-lh-ft clearance decided on was: Initial demand: 0.9 gpmlft' over 600 ft' Secondary demand: 0.50 gpmlft' over 2,000 f,'. To adjust for height use Figure 7-2.2.3: Initial demand: 108 percent X 0.9 gpmlft' = 0.97 gpmlft' Clear-Density Array 􀁾􀁮􀁳􀁩􀁴􀁹􀀠 D.y ;Density ance Fact. 0.91 0,97 600 1.00 .600 .600 2.000 LOO rea FacE. 􀀨􀁁􀁊􀁪􀀮􀁾􀀠Penalty tea (Adj.) (Adj.) NOIe3: 600 None 582 gpm 2.000 None None i.200 gpm Secondary demand: 120 percent X 0.50 gpm/ft' 0.60 gpm/ft'. To adjust for clearance use Figure 7-2.2.2: Initial demand: 1.00 X 600 ft' 600 f" Secondary demand: 1.00 x 2,000 ft' = 2,000 ft'. Conclusion: 0.86 gpm/£t2 over 756 ftt = 650 gpm lS-ft high storage 0.61 gpmlfl over 2,645 ft2 = 1,613 gpm ) 10-ft clearance 0.97 gpm/ftzover 600 􀁦􀁴􀁾􀀠 ::; 582 gpm I24.£t high storage 0.60 gpmlftl1 over 2,000 ft'< = 1.200 gpm 4-ft clearance The gratest gpm demand would be for 18-ft high storage and 10-ft dearance. Therefore. the protection sepdfied would be: Initial demand: 0.86 gpm/ft' over 800 ft' Secondary demand: 0.61 gpm/ft' over 2,600 ft'. (Areas should be rounded to nearest 100 ft\!.) 1990 Edition I APPEI"DlX C 231-27 C-4.3 As the commodity class increases in combustibility, or where storage could be easHy ignited from radiation, wider aisles should be provided. Smaller unit piies may be an alternative to wider aisles if yard space is limited. C-4.4 For outdoor idle pallet storage, see Section 4-4 and A-4-4.l.1 of this standard. Separation between piles of idle pallets and other yard storage should be as follows: Pile Sae Minimum Distance (Ft) Under 50 pallets 20 (6 m) 50·200 pallets 30 (9.1 m) Over 200 palleL<; 50 (l5.2 m) C-4.5 Boundary posts with signs designating piling limIts should be provided to indicate yard area. roadway and aisle limits. C.·5 Buildings and Other Structures. C-5.1 Yard storage, particularly commodities in [he higher heat release category, should have as much separation as is pF.lctical £l'om important buildings and structures, but not less than lhar offered by NFPA 80A, Recommended Practice for Proteclion of Buildings from Exterior Fire Exposures. C-5.LiAs guidance in using NFPA 80A in establishing clear spaces, the following Classification of Severity with Commodity Classes of this standard may be used on the basis of lOO percent openings reprcscnring yard storage: (a) Light Severity: Commodity Class L (b) Moderate Swcrily: Commodity Class II. (c) Interpolate between Moderate and Severe Severity for Commodity Class I II. (d) Severe Severity: Commodity Class IV and Class A plastics. NOT£.: '(1)(: aoove guidelines apply to the equivalent commodity classes of this standard. The 5cvcrity of the exposing building or !>tmcture s.hould also he a consideration when establishing a dear space. C·6 Yard Maintenance and Operations_ C-6.1 The emire storage site should be kept free from accumulation of unnecessary combustible materials. Vegetation should be kept cm low. Procedures should be provided for weed control and the periodic deanup of the yard area. e..G.! Adequate lighting shuuld be prQvided to allow supervision of an pans of the storage area at night. 􀁃􀁾􀀶􀀮􀀳􀀠 All electrical equipment and inslaiiations should conform to the provisions of NFPA 70, National Electrical Cod E$!'R 􀁳􀁰􀁲􀁩􀁮􀁊􀀼􀁬􀁾􀀠were used: "AutoIlWlc" K. "AulomaUc" Kl and Grinnell ESFR·1. Sprtnkler spacing was maintained at 10 ft by 10 ft (3 by J)1"'O.Mod 􀀧􀀺􀀧􀁵􀁾􀀧􀁾􀁊􀁬􀁜􀀮􀁑􀁲􀁬􀀮􀁬􀁬􀁬􀀩􀀧􀀮􀀠 Thre& addilionBlIast. _1Tit C;CnQuct.d!O InvQStlgate the case v.iIh Ignition centered between two sprtnlders, using !he Grin· nell ESFR-1 sprinkler. The _9" height was 35ft (10.6 m): the dearanea between spr/nkltilr th. \'e$!lng wilham any plugged head, the fin:: _ 􀁾􀁰􀁰􀁲􀁭􀁳􀀦􀁥􀁤􀀠with two 􀁨􀁥􀁡􀁾􀁳􀀠operating. Bec&1S8 of the plugged head test results, obslruc!lon !O c!l8bibutIon criteria "'" mor" 0IrI"9"nt. Tho last test w"", c:onducled!O InveaUgale whelhertha "Automalle" Model K1 􀁾􀁰􀁲􀁩􀁮􀁫􀁬􀁥􀁲􀀠c;culd successfully be U30d within the guIoe!lnes of this bule!ln. This test was 􀁾􀁲􀀮􀀠 -" Data Stleet 2·2 will be revI!led and proposals will be "",,,,,10 appropllale NFPA technical committees.. 􀁔􀁾􀁨􀁮􀁬􀁯􀀺􀁯􀁊􀀠AdVisory 􀁂􀁾􀁉􀁉􀁥􀁕􀁮􀁳 pmvldl!llnfarmatlon 101' II>SS ._1purpo..... TAB. reflect FaelOry MttlUal 􀀡􀁉􀁾􀀮􀁥􀀮􀀢􀀧􀁨􀀠COf'JIOl"IIIlon'" butludgment or 􀁾􀀠􀀬􀀢􀀬􀁢􀁾􀀠wh.... newn""" the nud for II!$! dOli!, Or lul1lTor ",.ean:h wlllll\(o!y 1_10 """"' rori8lon. In _ral, Ih..y provldo guldeUne$ b:> 􀁾􀁾.ud \'tI1h judument. 01992 Faetoty IolutuaI Engl."" • .,. Coif>, All rig,.. _. APPENDIX B-SUBDIVISIONS 2. Water services for each lot shall be stubbed out with an angle stop to the location required as shown on the standard details. A meter box conforming to the requirements of the standard specifications shall be installed over the end of each service. 3. Valves and fire hydrants shall be located at intsrvals of three hundred (300) feet in industrial, commercial or local retail areas and at intervals of five hundred (500) feet in apartment or residential areas. 4. Should the subdivision or addition abut and use a water main of the city. the developer shall pay to the Town of Addison a "pro rata" charge as prescribed by the pro rata ordinance of the city for use of the same. E. Other u.tilities. 1. The developer shall furnish all easements and rights-of-way necessary for construction of electrical, gas, and telephone service to the subdivision. 2. The developer shall pay for the number of street lights required in the subdivision as determined by the director of public works. Maximum distance between street lights shall be 'approximately six hundred (600) feet. After acceptance of the subdivision, service charges for electricity will be paid by the city. 3. The developer shall be responsible for all damage to improvements caused during installation of utilities. F. Miscellaneous, 1. The developer shall provide street signs for the subdivision. There shall be one sign for each three (3) way intersection and two (2) signs for each four (4) way intersection. The signs will be ordered by the public works department and the developer billed a fixed fee for each sign. Such price shall include cost of the sign assembly, pole and installation. 2. Sidewalks shall be constructed in accordance with the sidewalk ordinance of the Town of Addison on all lots Supp. No. 17 2109 10.401·10.501 1991 UNIFORM FIRE CODE of 150 feet from a water supply on a public street. as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains capable of supplying the required fire flow shall be provided when required by the chief. Type 01 Water Supply Sec. 10.402. Water supply may consist of reservoirs, pressure tanks, elevated tanks. water mains or other fix.ed systems capable of providing the required fire flow. In setting the requirements for fire flow, [he chief may be guided by [he provision in Appendix III-A. Fire Hydrants Sec. 10.403. The location, number and type offirehydrantsconnected tca water supply capable ofdelivering the required fire flow shali be provided on the public street or on the site of the premises Of both to be protected as required and approved by the chief. Fire hydrants shall be acce.<;sible to the fire department apparaLUs by roads meeting the requirements of Division II. For fire safety during construction, alteration or demolition of a building, see Section 87.103 (e). Division V INSTALLATION AND MAINTENANCE OF FIRE-PROTECTION AND UFE-SAFETY SYSTEMS General Sec. 10.501. (a) Type Required. The chief is authorized to designate the type and number of fire appljances to be installed and maintained in and upon all buildings and premises in the jurisdiction other than private dwellings. This designation shall be based upon the relative severity of probable fire, including the rapidity with which it may spread. Such appliances shall be of a type suitable for the probable class of fire associated with such building or premises and shall have approval of the chief. (b) Special Hazards. For occupancies of an especially hazardous nature or where special hazards exist in addition to the normal hal..ard of the occupancy, or where access for fire apparatus is unduly difficult, lhechiefis authorized lorequire additional safeguards consisting ofaddi[ional fire appliance units, more than one type of appliance. or special systems suitable for the protection of {he hazard involved, Such devices or appliances may consist ofautomatic fire alarm systems, automatic sprinkler or water spray sYSlems, standpipe and hose. fixed or ponable fire extinguishers, suitable fire blankets. breathing apparatus. manual orautomatic covers, carbon dioxide. foam, halogenated or dry chemical or other special fire--extinguishing systems. Where such systems are provided. they shall be designed and installed in accordance with the applicable Uniform Fire Code Standards. BAS Realty Ltd. 1223 Crowley Drive Carrollton, Texas 75006 Phone (214) 245-0252 Fax (214) 242-8203 JULY 23, 1996 JOHN BAUMGARTNER CITY OF ADDISON BOX 144 ADDISON, TEXAS 75001 DEAR JOHN: PER YOUR REQUEST AS ADVISED BY LYNN CHANDLER, BELOW YOU WILL FIND OUR CURRENT STATUS REGARDING VARIOUS SUBJECTS REQUIRED TO GET A TEMPORARY CERTIFICATE OF OCCUPANCY FOR MY PROPERTY AT 16400 MIDWAY ROAD. LANDSCAPE SLADE STRICKLAND HAS GIVEN ME THE MONTH OF AUGUST TO COMPLETE A SUBSTANTIAL PORTION OF OUR LANDSCAPING. AS WE ALL KNOW, AUGUST IS NOT A GOOD MONTH TO PLANT AND GOOD PLANTS ARE SCARCE, HOWEVER, WE WILL DO THE VERY BEST WE CAN. FIRE DEPARTMENT WE ARE CLEARED AND APPROVED. BRUCE MUELLER REQUESTED TODAY THAT WE DIG A THREE FOOT PERIMETER AROUND AND THREE INCHES BELOW THE FOUR (4) FIRE HYDRANTS ON THE PROPERTY TO MAKE OPENING THE WATER VALVES SIMPLE. THIS HAS ALREADY BEEN ACCOMPLISHED. UTILITIES BRUCE ELLIS NEEDS A MAINTENANCE BOND FROM OUR CONTRACTOR,TRIDALE COMPANY. BRUCE WAS PROMISED BY STEVE WHITE OF SUBJECT COMPANY TO HAVE THIS DONE BY THURSDAY OF THIS WEEK. BRUCE ALSO REQUESTED A CONCRETE 2X2 LOCATOR PAD CONTOURED TO FINISHED GRADE AROUND ALL FIRE HYDRANTS. THIS HAS ALREADY BEEN ACCOMPLISHED. JOHN, I THINK THIS COVERS OUR TEMPORARY C.O; REQUIREMENTS. PLEASE LET ME KNOW IF YOU NEED ANYTHING ELSE. 􀁾􀁾􀀠 V. A. AHM ------􀀭􀀭􀀭􀀭􀀭􀀭􀁾􀀮􀀭􀀮􀀭􀀭􀀮􀀭 􀂷􀀭􀀭􀂷􀀭􀀭􀀭􀂷􀀭􀂷􀂷􀀭􀀭􀁩􀀭􀀭􀁪􀁾􀁉􀀭􀂷􀂷􀀭􀂷􀀭􀂷􀁾􀀭􀀭􀀭􀂷􀀭 --􀀮􀁾􀀠 --==----\liY-/;I-----􀀭􀁉􀀭􀀭􀀯􀁾􀀭􀀭􀀭􀁾􀀠 ____􀁊􀀯􀁟􀀧􀁜􀁪􀁾􀀺􀀢􀀢􀀢􀁾􀀠 ._... 􀁾􀁾􀀭􀁟_􀀮_.._.... 􀁾􀁟􀁾􀁟􀁾􀁟􀀭􀀮􀀠 -------... 􀁾􀀭􀀭 __ 150"-􀁾.􀁾􀀠 .. r./7·Y 􀀾􀁾􀁾 .... 􀀭􀁾􀀭􀁾􀁾􀀭􀂷􀂷􀂷􀁾􀁬􀁬􀁩􀀠􀁦􀁎􀁾􀀬􀀠 ..... _. .. . . 􀀮􀀮􀀭􀀭􀁾...-...... -_. .. f.F" . -------.. . -\c;------. -···-1---· --.....-..-. ·----1 . . . 􀀧J􀁾I􀀧 􀁦􀀩)􀀠 􀁾􀀠 .. "'-" " .··---bvJl() -y.--.... -.. --􀀭􀀭􀁾􀀭􀀮􀀭􀀮􀀭....... 􀀭􀀭􀀫􀀭􀁾􀀭􀀭􀀭􀀭􀀭....----..I-.... ·.• 􀂷􀀮􀀮􀀭􀀭􀀭􀁾􀁟􀀭􀁾􀁟􀀽􀀱􀀷􀁾􀀭􀁃􀁾􀀠 -_. 􀀷􀁾􀀠 􀁾􀀮􀁟􀁟􀀽􀀭􀁟􀀮􀁟􀀽􀀭􀀭􀀭 -_.--__.-􀁾􀀽􀀠.-__ 􀁾􀀺􀀽􀁟􀀭􀀽􀁟􀀽􀁪􀁾􀀮􀁾􀁾􀀭􀀮􀁟􀀭 . __._.. __ __ /--------._------,-" --.. ..-..---..-..•.• _.._............. . _.....•.. _._._.._.}..-􀁾􀀠 ---.-. /V)\ , I . 􀁶􀀯􀀭􀁹􀂥􀂷􀁲􀀩􀁾􀀠 BAS REALITY LTD. 1233 CROWLEY DRIVE CARROLLTON, TEXAS 75006 (214) 245-2542 FAX (214) 242-8203 FEBRUARY 23, 1995 MR. RON WHITEHEAD, CITY MANAGER TOWN OF ADDISON BOX 1411 ADDISON, TEXAS 75001 DEAR RON, I KNOW YOU ARE AWARE OF MY PROBLEM BRINGING AN ELECTRICAL POWER LINE OVER THE DITCH FOR MY FORTHCOMING BUILDING ON MIDWAY. JOHN AND CARMEN SUGGESTED I WRITE TO YOU REQUESTING APPROVAL FROM YOU TO ALLOW ME TO PLEAD MY CASE TO THE CITY COUNCIL AT THE TUESDAY, MARCH 28, 1995 MEETING. I WILL SUMMARIZE THE PROBLEM BELOW SHOULD ANYONE LIKE TO REVIEW THIS MATTER PRIOR TO THE REQUESTED MEETING. THE TOWN OF ADDISON, APPENDIX B, SUBDIVISIONS, ORDINANCE #261 PAGES 2111 AND 2112 PROHIBITS THE USE OF INSTALLING ELECTRICAL POLES FOR OVERHEAD POWER USES. I THINK THIS ORDINANCE WAS MAINLY AIMED AT RESIDENTIAL DEVELOPMENTS OF WHICH I HEARTILY AGREE. HOWEVER, THIS ORDINANCE IF ENFORCED AGAINST MY MANUFACTURING FACILITY WOULD BE EXTREMELY COST PROHIBITIVE TO ME. HERE IN LIES THE PROBLEM. BELOW ARE OUR THREE OPTIONS: 1) TEXAS UTILITIES WOULD UTILIZE AN EXISTING POLE AT THE SOUTH SIDE OF THE DITCH AND RUN THE POWER OVER THE DITCH TO (1) INSTALLED POLE ON THE EAST END OF MY PROPERTY AND AS CLOSE TO MY TRANSFORMER AS POSSIBLE. WE WOULD THEN GO UNDERGROUND FROM THE POLE TO THE TRANSFORMER TO MY BUILDING. SIMPLE FOR TEXAS UTILITIES. VERY LITTLE COST TO ME. ONLY PROBLEM IS WE NEED A VARIANCE TO INSTALL (1) POLE AT THE REAR OF MY PROPERTY. 2) IF WE CANNOT GO OVER THE DITCH, WE HAVE TO GO UNDER THE DITCH. THIS WOULD ENTAIL BLASTING AND DRILLING A TRENCH APPROXIMATELY 3 FEET DEEP AND 2 FEET WIDE UNDERNEATH THE LIMESTONE DITCH. SECONDLY, SINCE THIS TRENCH IS SOMETIME UNDER WATER, SPECIAL CABLE, WIRING, AND CONCRETE ENCASEMENT WOULD BE REQUIRED BY CODE. THIRDLY, WE WOULD THEN HAVE TO GO FROM THE DITCH TO MY TRANSFORMER (APPROXIMATELY 150') UNDERGROUND IN ANOTHER CONCRETE ENCASEMENT TO HOUSE THE HIGH POWER WIRING. FOURTHLY, WE WOULD HAVE TO BUILD A MAN HOLE ON MY SIDE OF THE PROPERTY, SO TEXAS UTILITIES COULD INSPECT THE WIRING NEXT TO THE DITCH. COST ARE BEING TABULATED AT THIS MOMMENT FOR THIS OPTION. I HAVE BEEN TOLD THE COST WILL BE ASTRONOMICAL COMPARED TO RUNNING A SIMPLE POWER LINE OVER THE DITCH. 3) THE ONLY OTHER OPTION IS TO RUN THE HEAVY POWER LINES FROM THE CURRENT POLES ON MIDWAY TO THE REAR OF MY BUILDING WHERE THE PLANT IS LOCATED REQUIRING THE HEAVY ELECTRICAL USES. THE LENGTH IS ABOUT 700 FEET, WHICH AGAIN, THE HEAVY WIRING WOULD HAVE TO BE PLACED IN A SPECIAL CONSTRUCTED CONCRETE ENCASEMENT. THIS WOULD HAVE TO RUN THESE DISTANCES. AGAIN, COST FIGURES ARE BEING TABULATED BY TEXAS UTILITIES. THAT IS ABOUT THE SIZE OF IT. MY ONLY OTHER ALTERNATIVE WOULD BE TO PUT THE PLANT, SILO'S, ETC. IN THE FRONT OF THE BUILDING FACING MIDWAY WHERE THE POWER IS. THIS WOULD THEN PUT THE BEAUTIFUL FRONT OF MY BUILDING IN THE REAR FACING THE DITCHES AND CULVERTS. THAT CERTAINLY DOES NOT MAKE ANY SENSE FOR ME OR THE CITY OF ADDISON. RON, WE BOTH KNOW THAT IT IS VERY DIFFICULT FOR ANY ONE LAW OR ORDINANCE TO COVER ALL VARIABLES. I FIRMLY FEEL IT WAS NOT THE INTENT OF THE CITY COUNCIL, THROUGH PASSING ORDINANCE 1261, TO BRING THIS TYPE OF HARDSHIP ON A NEW BUSINESS THAT HAS SELECTED THE TOWN OF ADDISON AS ITS PERMANENT FUTURE HOME. THANKS AGAIN. REGARDS, J􀁂. 􀀩􀁾􀀹􀀻􀀻􀀷􀀠 A. SAHM GENERAL PARTNER VAS/mh/ Summary water Surface Calculations Entrance to 72" RCP February 8, 1995 The flow characteristics have been analyzed using the THYSYS computer program developed by the Texas Department of Transportation. The flows were taken from the Design Engineer's Report for the Addison Airport Drainage Improvements Project. The initial task was to determine the water surface elevation at the entrance to the 72" RCP prior to construction. Based on the survey data from the Addison Airport Drainage Improvement project and on the topographic maps provided by the Town of Addison, a cross section at station 59+17 (the entrance to the 72" RCP) was established. The western limit of the section is at elevation 614.9 approximately 85 feet west of the fence. The initial analysis inCluded only the flow from the drainage area north of the section. This analysis considered only the slope of the channel and the flow characteristics of the channel to compute the water surface elevation. This yielded the following: Q25 = 335 CFS water surface = 614.69 Q100 = 411 CFS water surface = 614.84 Examination of the topographic map indicated that this section carried not only the flow from the north, but also the flow from the east that crosses under the runway. Therefore, the initial analysis is not a realistic scenario. An analysis was made using the combined flows and the same section. Again, no backwater effects from downstream were considered. The initial computer simUlations indicated that the high point to the west at elevation 614.9 was not high enough to contain the water. Therefore, an imaginary wall was inserted at the high point with a very small roughness coefficient to simulate standing water at the edge of the section. The resulting water surface elevations are as follows: Q25 = 693 CFS water surface = 615.21 Q100 = 853 CFS Water surface = 615.37 This indicates that even with no backwater effects from downstream, the water was not contained within the channel, but flowed overland across the adjacent property. After reviewing the initial results, John Baumgartner requested that the water surface elevation prior to construction be evaluated using a section downstream from the entrance to the 72" RCP that appeared to be a constricting section on the topographic map. using survey information from the Drainage Improvements project, a section was evaluated at 280 feet downstream from the 72" RCP entrance. This section was evaluated as a constricting section using the slope of the channel and the flow characteristics of the section to calculate the water surface elevation at the downstream section. The water surface was then projected upstream to the 72" RCP entrance at the channel slope. This method shows the following: Q25 = 693 CFS HW25 @section 280' dwnstm. = 613.22 HW25 @72" RCP entrance = 617.45 Q100 = 853 CFS HW100 @section 280' dwnstm. = 613.62 HW100 @72" RCP entrance = 617.85 This water surface elevation is also above the 614.9 high point elevation on the property to the west, indicating flow over this property. Of the three scenarios examined above, the last probably gives the most reliable information regarding the water flow characteristics prior to construction. This section is very close to a surveyed section, contains all of the 100 year flow within the section for analysis, and represents a constricting section downstream from the 72" RCP entrance. The projection of a 100 year water surface elevation of 617.85 at the 72" RCP entrance indicates a significant backwater effect and shows that a significant amount of water flowed over the adjacent property to the west prior to the construction of the storm drain system. Determination of the exact elevation of the water surface and the split of flow between the channel and the overland flow would require a more complex hydraulic modeling effort and more information regarding the topography of the property west of the airport. The water surface elevation at the 72" RCP entrance has also been analyzed for the configuration after construction. The system was designed for the 25 year and included overland flow as a part of the design. The first constructed scenario assumed that the 72" RCP is in place and no fill was placed on the adjacent property. The water surface elevations with overland flow taken into account are as follows: Q25 = 335 CFS Water surface = 615.86 Q100 = 411 CFS Water surface = 618.74 The second constructed scenario was done assuming the 72" culvert is constructed and fill is placed on the adjacent property to the west. This is the existing condition. This analysis showed the following water surface elevations: Q25 = 335 CFS Water surface = 617.28 Q100 = 411 CFS Water surface = 618.99 The third scenario was done assuming 72" culvert is constructed and a retaining wall is placed 10' behind the fence. The water surface elevations are summarized as follows: Q25 = 335 CFS Water surface = 616.47 Q100 = 411 CFS Water surface = 618.86 It should be noted that all of the water surfaces were projected with the tailwater for the 72" RCP taken from the initial Engineer's Report and the tailwaters were calculated assuming that all of the flow is confined to the 2-7'x6' reinforced concrete box (RCB) downstream. with part of the flow being routed overland, the flow within the RCB would be reduced with a corresponding decrease in the tailwater elevation for the 72" RCP. All of the above scenarios show that some water would continue to flow overland as it did before the drainage system was constructed. After initial review of these three scenarios, John Baumgartner suggested that the water surface be evaluated using the 100 year tailwater calculated by the developer after the channel improvements were constructed. This tailwater was routed back through the drainage system and included the overflow area in the existing condition (fill has been placed on the adjacent property). The calculated water surfaces are as follows: Q100 = 411 CFS Water Surface = 618.57 The 25 year flow was not evaluated because no 25 year water surface elevation was provided by the developer's plans. All of the constructed scenarios indicate that the water flows overland around the pipe as it did prior to the construction of the drainage system. ." .' .. ;' .... TOWN OF ADDIsoN PuBLIC WORKS To: 3cbltaaCA2/From: John Baumgartner, P.E Director ' Company: i£Dc.L r/lS· ""ve eQuilled or cont.r1b\lt.ed to t.he concrete chilnn",l lining failure at. I:.h... referen/;.,d lo':at.1on, and pral!lant.ing PQllllilib!e aolut.ione to ;;!""v!mt ..maurr.nee. The following iii! my 􀁲􀁾􀁶􀁬􀀮􀁷􀀠of hi••t.Udy: As we have dillQulIIiled earlier. and aa tlr. Terrill 1IIt.e.ted in h1", rliport.. t.he damage was cliuaed by w..t...y byp....1ng an ax i!!!t l. n9 atorm .ewer pipe lo/;atlid on airport. 􀁰􀁲􀁯􀁰􀀮􀁲􀁴􀁾􀀠and flowing 􀁓􀁯􀁾􀁴􀁨􀀠 .!Ofig 􀁾􀁨􀀮􀀠 w••t. 􀁰􀁲􀁯􀁰􀁥􀁙􀁴􀁾􀀠 line of 􀁾􀁨􀀮􀀠airport, (al.o b.,1ng along your 􀁾􀁡􀁾􀁴􀀠 􀁰􀀮􀁬􀀰􀁰􀁥􀁲􀁴􀁾􀀠 line.) In describing t.he conditione which wart. pYElv10u.sly .xi.ting at. tbat. locstion. Mr. Tarrill .tat•• in hie report. that the top of the biilnk "whet! t.he pipe uae iniltal1ed l.I&a e ffi/w f",Slt, low.r" than t.he d ••ign headwater elevation, "allowing !JllltEir to flolJ overland west ,of the pipe." If t.hia w•• inda.d 􀁴􀀮􀁢􀁾􀀠 ca•• , it lJaa III QeriOU8 errOl", .1thar of 􀁤􀀶􀁾􀁩􀁧􀁮􀀠or oonstruction. !'II'. Tel'ri 11 fuy1;.heY et.at.e!! 1:.h8t tha o'irt.inty of ov· .101 by the 06lllign 25 y••r yaSlr atorm "did not. or••t. a major pr.)blem'. 'ilnd th.t. '_;--" larger flQr.Js foY the 50 year and 100 yellr d"., 'i ",t.OYI'fIS would also ",Ii "11ttl61 dlul'Iage", Thia wall. c.rtatnly '.:;C the time of ,:",nllt.ruoti on. b\i>OIlll\.liiill the land t.o the lJaat WOIiIi " ", .•,,'i,", 1 op.;,cl , howQver. 1-t· -'\iloulQ-be'::;orne moet ",mph_tie..lly falee I'ollo'.Iing devel",pmar.t. of t.h. land. Aw 􀁹􀁯􀁾􀀠 may recall, at our 􀁄􀁾􀁥􀀮􀁭􀁢􀁥􀁹􀀠meeting at. the Ctty 0' Addison, City Bng1neer John Baumgartner st.ated that h. w•• alao of the opinion that 􀁴􀁨􀁾􀀠wcet hank had b••n left lou et the time the pipe was in.t.lled. When I told him that 􀁷􀁯􀁾􀁬􀁤􀀠have b.mn either a de.ign or eon.truetion error, hil!! explanilt,ion \,IlUl t.bat. it. wa. done with th. int.ention that it wO\.lld be correoted 􀁾􀁨􀁥􀁮􀀠the adjacent property was dev.loped. However, ae you 􀁫􀁮􀁯􀁾􀀬􀀠 nr. aaumgart.nar not only didn't. notify you of .uch a neo•••ity 􀁷􀁨􀁾􀁲􀀮􀀠 􀁹􀁯􀁾􀀠began t.o develop tha adjacent property, but. had previously 􀁉􀁮􀁾􀀱􀁾􀁴􀁾􀁲􀁴􀀠 hhat th., fill dirt 􀁲􀀹􀁱􀁾􀁩􀁲􀀮􀁤􀀠for development of the adjacant. property ba placed a minimum of three feet. to the We.t of the 􀁰􀁲􀁯􀁰􀁥􀁲􀁾􀁹􀀠 line, 􀁴􀁨􀁥􀁲􀁥􀁨􀁾􀀠 prevent.ing even 􀁾􀁨􀀮􀀠 possibilit.y of fill being placed where 􀁩􀁾􀀠might provide eny aasis1:.ance 1n eQrreet.ing th. defieiancy _djacent to thQ b.adwal1. Also, 1 understand 􀁴􀁮􀀮􀁾􀀠 􀁡􀁾􀀠 nO 􀁾􀁩􀁭􀁥􀀠during the reviaw procQs$ not during 􀁯􀁯􀁮􀀮􀁴􀁲􀁾􀁣􀁴� �􀁯􀁮􀀠 of 􀁾􀁨􀁾􀀠channal linin; did h. 􀁬􀁮􀁤􀁩􀁣􀁡􀁾􀁥􀀠a 􀁮􀁾􀁷􀁤􀀠tQ correot i nacleq\.lat. bank hei ght. Qn the ai rport,. prQPlilrty. 3321 TOWEAWOOD DR.• SUITE 100 • FARM5RS BRANOH. TX 75234 • 214/247-1353 • FAX 214!247-2eaO FROM 214-241-26eo 01-13-Q5 􀀱􀀲􀀺􀀴􀀶􀀻􀁾􀀠 il02 2 fiG! I pol.nt.d Ol.ll;. at. our 􀁭􀁥􀀮􀁴􀁾􀁮􀁬􀁩􀀠 al:. t.h... Cit-y, L 􀀧􀁾􀀻􀀬􀀢􀀱􀀮􀀱􀁩􀀡􀁉 t.Q 􀁃􀁉􀀼􀀺􀀾􀁮􀁾􀁴􀀮􀁲􀁵􀁣􀁴􀀮􀀠 III (11" .. 11'1&;" stru.;::t.\U'a that. prov idea .. 􀀹􀀧􀀭􀀧􀀭􀁾􀀠 it. ulll nollvar rain hard l!I!'I.o1.lgh to flood it. Therefore, ,: ;!lOt II IJn,inaga fat;; 1Uty ovarflo\Jj1!, do.. not ne.:",.,,,,, ,EOd_ i flAdeqv$ t.il delltgn. There 61".. however, <::9rtd 1'1. 􀁥􀀧􀁾􀀧􀀺􀀬􀂷􀀠 Sl'! <::riteri& elllt...blisrhed to provide prot.ect.lon from 􀁩􀀧􀁲􀀬􀁧􀀬􀁱􀁾􀀧 ... ,'ll!nd tt-I.;I>, . achieve .. coat. effect.tve balanoGi b.t.waen c:ost. of '1d coat. of possible damage due t.o t.he probab11 1vI' ,-,-Among the most. basic of theJi!!lI! d.••ign paYllml!!t.Sl"jIj he th. !;lanK 01" a dr.insga channel muat. be at. llla.t. .11 h!ql' wat.ar surface. OthQrw1ee. by d$finition. t.h. d••ign ._ It. 􀁭􀁵􀁾􀁴􀀠 be 􀁣􀁯􀁮􀁾􀁬􀁵􀁤􀀮􀁤􀀮􀀠 bailed on My. 􀁔􀀮􀁔􀁲􀁩􀁬􀁬􀂷􀁾􀀠 􀁙􀀦􀁐􀁷􀁾􀀠 B..umgartner't!! .t..t.ement, that. t.he d.mlllgE! to the concl""'1;.& -.. th. Qirec:t result of en improperly 􀁣􀁯􀁮􀁥􀁴􀀮􀁬􀀢􀁵􀁾􀁴􀀮􀁤􀀠 drainagQ at whether 􀁴􀀮􀁨􀁾􀀠 error yas one of d••190 or of conetruot1on, ia the r ••ponwlbility lie. with t.he Cit.y of Addison. Con<;:ero1ng 0011"1"6<;:tLon of the exil!!lt.ing 1II1t1,lIltloo, io h11!i n;,pb'C't til". Terri 11 pr••"nt.1I t.wo possible mollthocls of prEiventing " 􀁴􀀧􀁾􀀢􀀧􀁾􀁲􀁲􀁾􀁮􀁃􀀸􀀠 of the 􀁾􀁹􀁯􀁢􀁬􀀤􀁾􀀮􀀠 neither of whioh do 1 f ••l would be 􀁁􀁯􀁥􀀮􀁰􀁴􀀪􀁢􀁬􀁾􀀠to you as t.he owner. Both option. inolude relooating a port1on ot the drainage flow onto your property, and const.ruet.ing.. 􀀧􀁾􀁬􀁬􀁥􀁬􀀠 drainage ¢¢\lrae on your property (li06d channel or storm aawe' 'a) in ord9Y t.O rali.ve the existing pipe and box culvert. 􀁬􀁯􀁾􀁾􀀠 on airport, propert.y. I If the 6x1.ting 􀁰􀁴􀁾􀀮􀀠 iw 􀁡􀁤􀀮􀁱􀁾􀁡􀁴􀁑􀁬􀁹􀀠aimed, 􀁴􀁨􀁾􀁙􀁾􀀠ehould b. no 􀁮􀁾􀁾􀁣􀁴􀀠 to conftbruob • parallel drainage 􀁦􀁡􀁣􀁩􀁬􀀱􀁾􀁹􀀠 in oydaY to reli8VQ It. Tha 100 Y0ar 􀁤􀀢􀁡􀁩􀁾􀁮􀀠W3tSY eurface. 􀁵􀁾􀁩􀁬􀁩􀁺􀁩􀁮􀁧􀀠Qnly t.he exlwting ?2-inoh pipe, t. 􀁬􀁮􀁤􀁴􀁾􀁾􀁴􀀮􀀮􀁤􀀠by 􀁾􀁲􀀬􀀠 􀁔􀁾􀁲􀁲􀀱􀀱􀀱􀀠•• b.ing elavation 􀁾􀀲􀀰􀀬􀀿􀀴􀀮􀀠 The plaoement of fill around the headwall to an elevation 􀁡􀁸􀁣􀀰􀁾􀁤􀀱􀁮􀁧􀀠 t.hat he!9ht. will effeotively prevent l"eourrenoe. at. a oon.iderabla lower coat 􀁾􀁮􀁑􀀠 without 􀁲􀁥􀁱􀁾􀁬􀁲􀀱􀁮􀁧􀀠the 10•• of additional land. The fill would be almost 􀁥􀁸􀁣􀁬􀁵􀁾􀁩􀁶􀁥􀁬􀁹􀁯􀁮􀀠airport property, but. would 􀁲􀁾􀁱􀁵􀁩􀁲􀀸􀀠the removal and 􀁲􀁥􀁰􀁬􀀮􀁣􀁥􀁭􀁾􀁮􀁴􀀠of the airport. pounQary fanoe. All fill shOUld reoeive adequate compaction and be placed under t.he direction of • Yl!!gisterad aoils engineer, If t.b. City Should f.el that. .levation 920.74 would be too hlgh to allow 􀁷􀁾􀁴􀀮􀁲􀀠to baCK 􀁵􀁾􀀠on airport prop.rty, an .1ternativQ .olut.ion would be to install a aaaonQ atorm ••􀁾􀀮􀁲􀀠pipe p.r.ll.l t.Q t.ha 􀀪􀁾􀁩􀀮􀁴􀁩􀁮􀁧􀀠 ?2-inah p1pe. in ord.r to lowar t.he design bacKwat.er 􀁥􀀴􀁾􀁶􀁡􀁴􀁩􀁯􀁮􀀮􀀠 􀁔􀁨􀁾􀀮􀀠 construction would taka 􀁰􀁬􀀤􀁾􀁡􀀠on airport. property. anQ would be a 􀁭􀁵􀁾􀁨􀀠 fthorter distance than would b. requlred requlred by r610eating t.he flow onto your property (appYoximately Be feet 􀁙􀁡􀁾􀁨􀀮􀁲􀀠that 400 f ••t), t am .nQlo.ing a eopy of Mr. Terrill'••􀁴􀁾􀁤􀁹􀀠 for your informat.ion. If I may b. of any further assiat.ance in this matter, pleaae do not h.sit.ate to call. CS\1 􀁮􀀻􀁥􀁾􀁥􀁬􀁹􀀮n \u......t ( 􀁙􀀮􀁊􀀡􀁾􀀯􀀯􀀮􂂬 􀂷 Robert. 􀁾􀀮􀀠 􀁐􀀮􀁡􀁲􀁾•• P.E. FROM ZI4-2'7-2680 O! 13-9S 12;45 PM P03 􀁇􀁲􀁾􀀠 r, Inc. 4100 Amon Carter Blvd., Suite 10B Fort Worth, Texas 76155 (817) 545·0891 FAX: (817) 545·0534 Greiner December 15, 1994 Y8024.62 Mr. John Baumgartner, P.E. Director of Public Works Town of Addison P.O. Box 144 Addison, TX 75001 Reference: Addison Airport Drainage Summary -West Side Outfall Dear Mr. Baumgartner: Enclosed is a copy of the Drainage Summary and some exhibits concerning the riprap failure and the drainage in the area we discussed last week. Please review it and let us know if you need further information for this area. If any questions or need further information, please call. Sincerely, GREINER, INC. 􀁊􀁾􀀧􀁊􀁾􀁦􀀮􀁅􀀠 Tracy L. Terrill, P .E. Project Engineer Addison Airport Drainage summary West Side outfall Riprap Failure December 9, 199. The area in question is on the west side of the airport from the outfall of the double 7' x6' RCB north to the end of the 72" RCP and the area of riprap that was overturned in the open channel adjacent to the storm drain outfall. The land west of the airport property has been filled and raised significantly within the last few years. The riprap failure was probably caused by a high water level behind the riprap that was not balanced by an equal water level in the channel. This resulted in the riprap being overturned. In addition, erosion has occurred along the fence line. Some fence post foundations have been undermined and others are exposed to a significant depth. The water causing the damage is flowing around the 72" RCP running north of the double 7'x6' RCB along the west property line of the airport. This system was designed for a 25 year rainfall event. According to the Design Engineer's Report for the Runway and Taxiway Drainage Improvements, the headwater elevation at the upstream end of the pipe is 617.16 feet if the 25 year peak flow is confined to the pipe. The ground elevation directly over the pipe is approximately the same as the 25 year headwater. The existing elevation of the ground at the fence line and on the adjacent property when the pipe was installed was a few feet lower allowing water to flow overland west of the pipe in the existing overflow area during high flow periods. This did not create a major problem because the water had a large area to flow through and therefore flowed at low velocity. The larger flows for the 50 and 100 year events were similarly spread over a large area with little damage. When the land within this overflow area was filled, the area available for flow was reduced resulting in higher headwaters and velocities. In addition, the toe of the fill slope is very close to the fence. This directs the flow along the fence line where erosion damage is least tolerable. Also, when the riprap was placed on the north bank of the open channel by the developer, no provision was made to accommodate the flow from the existing overflow area west of the pipe. As a result, the water from the overflow area gathered behind the riprap and pushed it over. The problem may be solved by removing the fill in the area adjacent to the fence to allow the water to flow as it did previously with an outfall built to direct the water into the open channel. Another alternative is to add another pipe from the headwall to the open channel. In either case the outfall at the open channel should be designed to direct the flow in the same direction as the normal flow in the channel or the opposite bank improved to protect against erosion. Greiner Job Adti/f;120 k"rpui: Proja<:! No, ______ Sheel Oescription __________ Computed 8y _____ Oate ____ _____________ Checked8y ______ DOI9 ____ 􀁾􀁾􀀠 -( 􀁾􀀠 "1 "l '-􀁾􀀠\I ul '" 􀁾􀀼􀁴􀀠 ! I ,f I I 􀁾􀀠 'Il:: " 􀁾....... 􀀠 r-::: ....... 􀁾􀀠 " 􀁾􀀠 "" '􀀮"􀁾*􀀠 :;;: 􀁾􀀠 􀁾􀀠 􀁾􀀠 \\ '-. "\;, \J c: ..:::::: c: ".":; ''"'" 􀁾􀀠 ;: -"" Qf I 􀁾􀀠 -+ 􀁾 r-,"> 􀁾.. 􀁾􀀠 􀁾􀀠 S! 􀁾􀀠 11 􀁾􀀠 l\.l ?l ::t: 􀁾􀀠 􀁾􀀠 PIOi.' /t2 a1f)Y1j £ht/!Jnelaf "L-7Xf I RCf ovitt/II Fa?",!} /Vorfl] 51 5 􀁾􀀬􀀠 tr i' " g 􀁾􀀮􀀠 V ferJc-e /' Top of /?';rm? svqqe",-reJ Ovev.f-/ow /􀁟􀀺􀁉􀀮􀁮􀀬􀁾􀁦􀀭􀁡􀀯􀁬􀁥􀁤􀀠by pevefocer /oV'l-'t-«/1 CIJt'tr&r1 I) 'Z /.£V!)!jt'5 i-d Po rye:..:::c,';( --" /C FE Open c;.han ne.f vv+f!.al/(Otfuml) "'\. \ /\,;,.1 _ r-----0 0 "1l :r 0 .2. il? 3 m 2-7X/R{J? $ c. '0 ! 0 􀁾 JJ-----􀁾􀀠 " II z 􀁾􀀠 􀁾􀀠 f • • -----------• • • TOP BANK EXIST. DITCH EXIST, 2 -42' RCP EXIST, 54--R.C.P. /NOTE:SEE GRADING DETAILS nilS AREA. I...I-_-:--EXIST. CONe. 􀁟􀁾􀀭􀀽􀀭􀁉􀀠 HEAD'vIALL 1\ ;--/n 􀁯􀁉􀀨􀁲􀂣􀀼􀀭􀁉􀀧􀁾􀁮􀀠 //////---15 FO -(-SEESHEETS 23-24. 􀁾􀀠 CONST. 8 L.F. 􀁾􀀠 W/CONC. PLUG) 1---1 1 1 􀁾􀀮􀀮􀀮􀀭􀀭􀀭 --/EXIST. HEAD'vIALL (TO BE REMOVED) >-IEXIST. 2-66' R.C'p. 1 1 a: /. • //11'/II /I fI1 f'rtlve 0f//,o,S,'1c3 krn/r OY Redl,..",,,,,'! -filo...... /".p ..p/t;w I,., c h"pt hel. //EXf£1=-. LINE "1"---" 2-7' X 6' 66-R.C.P. -􀀸􀀸􀁾􀁾􀁒􀀢􀁏􀁘􀀠 􀁄􀁉􀁔􀁃􀁾􀀠 SHEET 2-7' X 5' _...-: IN CONC. BOX CULVERT (SEE SHEET 22' OF 30" R.C.P. @1.00% (CAP END 3' X 6' BOX CULVERT 1 􀁜􀁾 r VASIl)\<{_ • LINE "G" · ) I"1""" \..-VASI • •• .... REMOVE & REPLACE .... N 20° 23' W 􀁾S. Y 0:AVEMENT .... & .... • . ."'-(.. . """ • • • • • JAN-05-1995 15:06 FROM r'EINER INC. 113 TO BAUMGARTNER P.01 f (,j--. :'I" 1'(./'. Greiner. Ioc. 4100 Amon c..rter Dlvd•• :Jult<> 1Oil Fort Wortn, Texas 76155 (8171 546·0891 FAX: (817) 545-{)534 Greiner ,._--_.,,_.. ""...􀀭􀀭􀀭􀀭􀀭􀀭􀀮􀀭􀀭􀀭􀀭􀀭􀁾􀀬􀀠 December IS, 1994 YS024.62 Mr. lohn Baumgartner, P .E. Director of Public Works Town of Addison P.O. Box 144 Addison, TX 75001 Post·i!-F-ax Note 7671 To::[" hI'i B",. Aner CO./OePt. Pf1<>ro> • Fax , -, ....or -------,--Da'" !-5-fS It.gV'g Fro", -I (''':;1/• r'.-.B. fro 'II Co, PhonGfi Fax I I Addison Airport Drainage Summary -West Side Outfall Dear Mr. Daumgartner: Enclosed is a copy of the Drainage Summary and some exhibits coneeming the riptap failure and the drainage in the area we discussed last week. Please review it and let us kIrow if you need further infonnation fot this area. If any questions or need further infunnation, please call. Sincerely. GREINER, INC. 􀁊􀁾 􀁴􀀮􀀻􀁪􀁾􀁦􀀮􀁅􀀠 Tracy L. Terrill, P .E. Projecr Engineer JAN-05-1995 15:07 FROM EINER INC. 113 TO BAUMGARTNER P.02 Addison Airport nrainaqe summary West Side outfall Riprap Failure December 9. 1'" The area in question is on the west side of the airport from the outfall of the double. 7'x6' RCB north to the end of the 72" RCP and the. area of riprap that was overturned in the open channel adjaoent to the storm drain outfall. The land west of the airport property has been filled and raised significantly within the last few years. The riprap failure was probably caused by a high water level behind the riprap that was not balanced by an equal water level in the channel. This resulted in the riprap being overturned. In addition, erosion has occurred along the fence line. Some fence post foundations have been undermined and others are exposed to a significant depth. The. water causing the damage is flowing around the 72" RCP running north of the double 7'x6' RCB along the west property line of the airport. This system was designed for a 25 year 􀁲􀁡􀁩􀁮􀁦􀁡􀁾􀁬􀀠event. event. ACCOrding to the Desiqn Engineer's Report for the Runway and Taxiway Drainage Improvements, the headwater elevation at the upstream end of the pips is 􀁾􀀱􀀷􀀮􀀱􀀶􀀠feet if the 25 year peak flow is confined to the pipe. The ground elevation directly over the pipe is approximately the same as the 25 year headwater. The existing elevation of the ground at the fence line and on the ad1acent property when the pipe was installed was a few feet lower allowing water to flow overland west of the pipe in the existing overflow area during high flow pedOO!L This did not create a major problem because the water had a large area to flow through and therefore flowed at low velocity. The larger flows for the 50 and 100 year events wers similarly spread over a large area with little damage. When the land within this overflow area was filled, the area availabl';' for flow was reduc""d resulting in higher headwaters and velocities. In addition, the toe of the fill slope is very close to the fence. This directs the flow along the fence line where erosion damage is least tolerable. Al1'lo, when the riprap was placed on the north bank of the open channel by the developerI no provision was made to accommodate the flow from the existing 􀁯􀁶􀁾􀁲􀁦􀀱􀁯􀁷􀀠area west of the pipe. As a resu]t, the water from the overflow area gathered behind the riprap and pushed it over. Th .. problem may be solved by re1lloving the rill in the area adjacent to the fence to allow the water to flow as it did previously with an outfall bu;Ut to direct the water into the open channel. Another alterna:tivl;> is to add anothe.r pipe from the headwall to the open channel. In either case the outfall at the open channel should be designed to direct the flow in the same direction as the JAN-05-1995 15:08 FROM F1EINER INC. 113 TO BAUMGARTNER P.03 /.,.. normal flow in the chann@l or the opposite bank improved to protect against erosion. JAN-05-1995 15:09 FROM 1EINER INC. 113 TO BAUMGARTNER P.05 Greiner Job ________________ -______ 􀁾__of__ Compvted By 􀁾..... PrQject No. 􀁟􀁾􀁾__ Date ___􀁾􀁟􀀠 􀀭􀁾􀀭􀁾􀀭􀀭􀀭􀀭􀀭􀀭􀀭􀀭􀀭􀀭􀀭 C!lecI '< I r-, I 1 􀁾􀀠 􀁾􀀠 "-'.SI-,:.,.., ",􀁾􀀠 ;!: () .... 􀁾􀀼􀀺"􀀾􀀠 􀁾􀀧􀀭􀁊􀀠 " " " 􀀬􀀮􀀮􀀭􀀭􀁾􀀠 􀁾􀀺􀀺􀀺􀀺􀀠 ( \ /􀁾􀀠 /J//. ! 1 􀁖􀁪􀁾􀀠 j '>..JS 􀁾􀀠 i"{ -".;,;. CL:: 􀁾􀀠 -... --;. 􀀮􀁾􀀠 "'􀁾􀀬􀁾 .' 􀁾􀀠--􀁾􀁾􀀠 %:'"! '-I)..., I -, '>i ; :>;;; I ..s'":. 􀁾􀀠 s'"o ""' Q, I:!:I. I,, JAfj-05-1995 15:08 FROM 􀁾􀁅􀁉􀁈􀁅􀁒􀀠 IHC. 113 TO BAUMGRRTHER P.04 Greiner ProjGct No. ______ Shoot __􀁯􀁦􀁾􀀠 DeSGfipli"" ___,________ eo"""""",8y Daw _____ ______.____. ___ Ch9Ckaday 0..101 _____ I ,I ..........t, 1 J 􀁾􀀠 .J;:: ( t \\ 􀁾􀀠 􀁾􀀠 􀁾􀀭􀀭 􀁾􀀠 )r: 􀁾􀁾􀀠 􀁾􀁾􀀠 􀁾􀁨􀀠 􀁾􀀠􀁾􀀠 􀁾􀀠 􀁾􀀠 􀀬􀁾􀀠 '>l) 􀁾􀀠 M \' . 􀁾􀀠 '\-.. ..., 􀁾􀀠 \l 􀁾􀀠 \::: 􀀮􀁾􀀠 􀁾􀀠 \) 􀁾􀀠 ;t "\t;, ...... 􀁾􀀠 "...... 􀁾􀀠 􀁾􀀠 Ii II '" V, i£ 􀁾􀀠 ::t:: 􀁾􀀠 􀁾􀀠 <'l;-􀁾􀁾􀁉􀁉􀀧 II' JAN-05-1995 15:09 FROM r"'j:EINER INC. 113 TO BFU1GARTNER P. 06 I fY}f'rtJve 􀀰􀁦􀀯􀀬􀁩􀀧􀁬􀁓􀁲􀀧􀁾􀀠 l ' 􀁬􀀿􀀻􀁦􀀻􀀡􀁤􀁬􀁾􀁉􀀧􀁲􀁾􀀮􀀺􀁉􀀠 􀁾􀀯􀁾􀁉􀀭􀀭 /» d,";c; . ".f 􀁾IQU; ; '" eh4:1lI ;el. 30<'!?C 􀁐􀀢􀀧􀁦􀂥􀁩􀀱􀀬􀁾􀀭􀀧􀀭􀀧􀀭􀀭􀁾􀀪􀀢􀀭􀀧􀀭􀀽􀀭􀀮􀀭􀁃􀀮􀀭􀀭􀀽􀀮􀀽􀀮􀀮􀁾􀀽􀀭􀀭 , TOP BANK EXIST, DITCH 􀁾􀁾􀁾􀀮􀀠 -..---"" -------" I __ , __ _ 54" R.C.P. LINE "1"-" W R.C.P. --" .----􀁾􀀠/NOTE:SEE SHEET 15 F , S-4 ( GRADING DETAILS IN ntis AREA. 􀁾􀁟􀀭􀀺􀀭􀀭􀁅􀁘􀁉􀁓􀁔􀀮􀀠CONe. _-.ll.-;::""! HEAn\.lAI l. 􀁅􀁘􀁉􀁓􀁔􀀮􀁾􀀠 6' BOX CULVERT 1\ 􀀩􀀭􀀭􀀭􀁾􀁳􀁳􀀠 3' X I 􀁜􀁾􀀠 -"-_ r VAS1 1 r􀁜􀁾􀁟􀀠 • J I 􀀱􀁾􀁾􀀠 􀀭􀀭􀀭􀀭􀁾􀀭􀀭􀀭􀀭􀀭􀀭􀀭􀀭􀀭􀀭􀁾􀂷􀁾􀀭􀀭􀀭􀀭􀀭􀀭􀀭􀀭􀁾􀂷􀀯􀁾􀀭􀀭􀀭􀀭􀀧􀀴􀀫􀀢􀀭􀀭􀂷􀀭􀀭􀁾􀂷􀀭􀀭􀀭􀀭􀀭􀀭􀀭􀀭􀂭 I N 20° ,; . . 􀁾􀀠 ;. -----------, • (.. 􀀮􀁾􀀠 ------• • JAN-05-1995 15:10 FROM 􀁾􀁅􀁉􀁎􀁅􀁒􀀠 INC. 113 TO ) BAUMGARTNER P.07 I I 11';' /1 /[ fJ1 f' rtJve of'posd(J &.:t",k t:w ?􀀴􀁬􀁤􀁊􀀢􀁩􀀱􀁯􀀢􀀴􀀡􀀡􀁾􀀠 --A1t;7f,.f.-iit 􀁤􀁾􀀧􀀧􀀧􀀧􀁾􀀯􀁔􀀧􀀧 􀀼􀀱􀀱􀀷􀀠 //,p yt.'/P'V ;" 􀀮􀁴􀀻􀁨􀀴􀁾􀀠he/. /////I /LINE 􀀢􀁉􀀢􀀭􀁾􀀠 2-7' X 6' -66-R.C.P. --:------8&'"iR"OX P. (SEE SHEETS 23-24) . _----􀀭􀀭􀀭􀀭􀁾􀁾􀀭􀂭 E:SEE SHEET 15 2-7' X 6" 􀁾􀀮􀀮􀂭 ,DING DETAILS IN CONC.BOX ; AREA. CULVERT CONe. (SEE SHEET 22) D\JALL CONST. 8 l.F. Of 30" R.C.P. @1.00%{CAPENDW/CONC. PLUG) tJ.-----1 -• LINE "G" 􀁾􀁖􀁁􀁓􀁉􀀠• REMOVE & N 20° 23' W 􀁾􀁓􀀮􀁙􀀮􀀠PAVEMENT --ZtP'7J.. &. J. '------------------.... ! I I /. • ...----/ (SeE SHEETS 23-24) 􀁾􀀭􀀺􀀠 I !-----1 I I I II fa <0 II /. --.. j(---......EXIST. HEAD¥lALL (TO BE REMOVED) EXIST. 2-66'· R.CP. ••• JAN-05-1995 15: 10 FROM 'EIt"ER INC. 113 TO -􀁂􀁁􀁕􀁾􀀱􀁇􀁁􀁒􀁔􀁎􀁅 􀁒􀀠 P. 08 ///,/II I /////////2-T X 6' 8frgeR"OX 2-7' X 5' CONe. BOX CULVERT (SEE SHEET 22' CONST. 8 LF. OF 30" R.C.P. @1.00% (CAP END W/CONC. 􀁾􀀩􀀠 -􀁾􀀭􀀭 • LINE "G" "'-VASI • /. & REPLACE , 􀁗􀁟􀁾􀁾􀁾􀁳􀀮􀁙􀀮􀀠PAVEME_NT__ !b. £/5'O-;z.J37! /'c1cf3 L/So 2'6'39 .()O METER NUMBER UNITS CURRENT PREVIOUS USAGE; 􀀰􀀴􀀯􀁾􀁾􀀯􀀹􀀴􀀠 􀁏􀁾􀀯􀁾􀁏􀀯􀀹􀀴􀀠 ,19 􀀨􀁾􀁉􀀡􀁉􀀺􀁬􀁉􀁥􀁈􀀧􀀭􀀧􀁖􀀠 ·!'(;'A\.. 4 ... fih:;u" \I I c; «fi Ct:rruu ump 1" I can/R.m i 􀁾􀀠 􀁃􀁨􀁾􀀧􀀨􀀧􀀹􀁗􀁩􀀠 wp.-I·a;:R () 􀁔􀀼􀀺􀀬􀁾.. 1. "''''.00 •.___o" seRVICE PERIOD DAYS METER NUMElER UNITS CUAI9I:NT PREVIOUS USAGlE 041';21/<;>4 Ot!l/:i!()/94 􀁾􀁷􀀠 􀁡􀁯􀀻􀁾􀁥􀀻􀀢􀀧􀁎􀀠 '1"""'1_ 34.... i 􀁥􀀻􀀻􀁾􀁦􀀮􀁉􀀺􀁩􀀡􀀠 7IlI San" v 1􀁣􀀮􀁾􀀠 􀁃􀁃􀀧􀁊􀀩􀀧􀁣􀀻􀁾􀁴􀀮􀁴􀁵􀁰􀀠t I 􀁴􀀺􀁾􀁮􀀯􀀧􀁾􀁬􀁉􀁊􀀭􀁴􀀧􀀨􀀪􀀠 Ch..rOIf: 􀁗􀁁􀁔􀁾􀁾􀁦􀁾􀀠 'fm 􀁾􀀱􀁾􀀱􀀠"I O'i' WAW'I'li1:WA'rI!!:R 􀀢􀁾􀁉􀀠 11.39.9..1. ""1> '\' •• l ANICH,,':)U, 'fc'l'" r.:n'"'c:unIJ)'t" ,"lI1:yfllfPIl'l"t (.l f" Y(!HH' Prien!. I\!".I'O,. 􀁁􀁾􀀮􀁉􀀢􀀠I l to I t I. 􀀱􀀱􀀱􀁾􀀡􀀠• fo"v t.'.."...-I 􀁾􀁾􀀮􀁴􀀠􀀠 ,•.'d.. L", I.•' .􀁾􀁦􀀱􀀧􀁾􀀭􀀭􀁾􀀭􀀢􀀢􀀠 ,"1(:iD!!io-cev I ..,'. ,t·ltd.!!Zlt;;.. 􀀮􀀮􀁾􀀠., %L1./f...􀀱􀀮􀀮􀁁􀁾􀀮􀀮􀀮􀀮􀀮􀀠 .. .... Paid Ch(;lcll ,I· 􀁾􀀦􀁬􀁦􀀷􀀧􀁻􀀩􀀠􀁄􀁡􀁬􀁥􀁤􀀦􀀹􀁌􀁦􀀺􀁴􀀻􀁾 􀁾􀀠 I FOR BILLING INQUIRIES PLEASE GALL 466-3120. AFTER HOURS AND FOR EMERGENCIES PLEASE 􀁃􀁁􀁾􀁌 486·3425